Technical data

Table Of Contents
Events
System Software for S7-300/400 System and Standard Functions - Volume 2/2
34-14
A5E00739858-01
Event ID Event OB
W#16#75DF/74DF Start / end of F program initialization -
W#16#75E1 Safety program: Error in FB "F_PLK" or "F_PLK_O" or
F_CYC_CO" or "F_TEST" or "F_TESTC"
W#16#7934 Standby-master switchover due to connection problem at the
SYNC module
OB 72
W#16#7950 Synchronization module missing OB 72
W#16#7951 Change at the SYNC module without Power On OB 72
W#16#7952/7852 SYNC module removed/inserted OB 72
W#16#7953 Change at the SYNC-module without reset OB 72
W#16#7954 SYNC module: rack number assigned twice OB 72
W#16#7955/7855 SYNC module error/eliminated OB 72
W#16#7956 Illegal rack number set on SYNC module OB 72
W#16#7960 Redundant I/O: Time-out of discrepancy time at digital input, error
is not yet localized
W#16#7961 Redundant I/O, digital input error: Signal change after expiration
of the discrepancy time
W#16#7962 Redundant I/O: Digital input error -
W#16#796F Redundant I/O: The I/O was globally disabled -
W#16#7970 Redundant I/O: Digital output error -
W#16#7980 Redundant I/O: Time-out of discrepancy time at analog input -
W#16#7981 Redundant I/O: Analog input error -
W#16#7990 Redundant I/O: Analog output error -
W#16#79D3/78D3 Communication error between PROFIsafe and F I/O -
W#16#79D4/78D4 Error in safety relevant communication between F CPUs -
W#16#79D5/78D5 Error in safety relevant communication between F CPUs -
W#16#75E2 Safety program: Area length error -
W#16#79E3 F-I/O device input channel passivated -
W#16#78E3 F-I/O device input channel depassivated -
W#16#79E4 F-I/O device output channel passivated -
W#16#78E4 F-I/O device output channel depassivated -
W#16#79E5 F-I/O device passivated -
W#16#78E5 F-I/O device depassivated -
W#16#79E6 Inconsistent safety program -
W#16#79E7 Simulation block (F system block) loaded -