Technical data
A.8 Technical data: LOGO! 12/24... LOGO! DM8 12/24R
LOGO!
336 Manual, 04/2011, A5E03556174-01
LOGO! 12/24RC
LOGO! 12/24RCo
LOGO! 12/24RCE
LOGO! DM8 12/24R
Short circuit-proof cos 0.5 to
0.7
Power protection B16, 900A Power protection B16, 900A
Parallel output circuits for
power increase
Not permitted Not permitted
Protection of output relay
(if desired)
max. 16 A, characteristic B16 max. 16 A, characteristic
B16
Switching rate
Mechanical 10 Hz 10 Hz
Ohmic load/lamp load 2 Hz 2 Hz
Inductive load 0.5 Hz 0.5 Hz
Notice: For fluorescent lamps with capacitors, the technical data of fluorescent lamp ballasts
must also be considered. If the maximum allowed surge current is exceeded, fluorescent
lamps must be switched with appropriate contactor relays.
The data was determined with the following devices:
Siemens fluorescent tubes 58W VVG 5LZ 583 3-1 uncompensated.
Siemens fluorescent tubes 58W VVG 5LZ 583 3-1 parallel compensated with 7μF.
Siemens fluorescent tubes 58W VVG 5LZ 501 1-1N with ballast.