User Manual

11
If the room occupancy times of the various geographical zones are identical, a time
switch can be defined as the master. Then, the other controllers as time switch slaves
adopt the occupancy times from the master.
Setting the geographical zone with identical room occupancy times but different
operating modes.
If 2 ventilation plants or 1 heating circuit and 1 ventilation plant supply the same
rooms, they also have the same geographical zone. The 2 plants acquire the same
room temperature and use the same room occupancy schedule (room operating mode
is the same). If the room operating mode is changed via the presence button on the
room unit (e.g. on the QAW740), the room control master adopts the change and for-
wards it to the room control slave. In the case of a room control combination of heating
circuit and ventilation plant, the ventilation plant always provides the function of the
room control master.
Setting the geographical zone with identical room operating modes.
It can be selected whether or not the demand for heat or cooling energy shall be for-
warded to the heat or refrigeration source. For example, a refrigeration machine is put
into operation only if the evaluated demand exceeds an adjustable level (path: … >
Settings > Refrigeration demand).
The demand for heat or cooling energy can also be forwarded via a relay or a DC
0…10 V signal (path: … > Commissioning > Extra configuration > Heat demand /
Refrigeration demand).
This document only describes the settings for communication. For the configuration
and parameter settings to be made on the individual devices, refer to the respective
application sheets
When preparing the settings for communication, we recommend to make use of the
"Synco
TM
Planning and Commissioning Report C3127"
Geographical zone
Heat demand /
refrigeration
demand
Notes on planning
RM..
RM..
Slave
Master
3150Z07en
Time switch
Time switch
Ventilation 1
Heating circuit 2
Geogr zone = 1
Geogr zone = ---
TS slave (Apartm.) = ---
TS slave (Apartm.) = 1
QAW740
RM..
RM..
3150Z08en
Geogr zone = 5
Room unit
Room operating mode Room operating mode
Geogr zone = 5 Geogr zone = 5
Ventilation 1
Room control comb. =
Master
Room control comb. =
Slave internal setpoints
Heating circuit 1