User Manual
21
Parameter settings
for communication
Parameter Setting Function Remarks
1. Parameter settings on the refrigeration controller, RMS705B
Basic settings
Path: ... > Commissioning > Communication > Basic settings
Clock time opera-
tion
Slave The device receives the time of day
from the master
Remote setting
clock slave
Yes The master’s clock can be set from
this device
Remote reset of
fault
Yes Faults of other bus users can be
acknowledged and reset from this
device
Settings for the distribution zones
Path: ... > Commissioning > Communication > Distribution zones
Outside tempera-
ture zone
1 The device receives the outside tem-
perature via outside temperature
zone 1
Refrigeration
distribution zone
1 The device receives the refrigeration
demand via refrigeration distribution
zone 1
To enable the controller to give
consideration to refrigeration de-
mands, it must be internally con-
nected to function block ”Refrigera-
tion demand”
For example: Commissioning >
Extra configuration > Controller >
Controller 1 > Universal shift =
Refrig request mod
2. Parameter settings on the heating controller, RMH760B, basic type H4-0
Basic settings
Path: ... > Commissioning > Communication > Basic settings
Clock time opera-
tion
Slave The device receives the time of day
from the master
Remote setting
clock slave
Yes The master’s clock can be set from
this device
Remote reset of
fault
Yes Faults of other bus users can be
acknowledged and reset from this
device
Settings for the distribution zones
Path: ... > Commissioning > Communication > Distribution zones
Heat distribution
zone
1 The device receives the heat de-
mand via heat distribution zone 1
Outside tempera-
ture zone
1 The device receives the outside
temperature via outside temperature
zone 1
3. Parameter settings on flow temperature controller RMU710B, basic type C
Basic settings
Path: ... > Commissioning > Communication > Basic settings
Clock time opera-
tion
Slave The device receives the time of day
from the master
Remote setting
clock slave
Yes The master’s clock can be set from
this device
Remote reset of
fault
Yes Faults of other bus users can be
acknowledged and reset from this
device