User Manual

23
Parameter Setting Function Remarks
5. Parameter settings on room controller 1, RXB22.1/FC-12
Settings for the zones
Path: ... > Communication
Geographical zone
(apartm)
4 Room group number
Geographical zone
(room)
1 Room number
Geographical zone
(subzone)
1 Number of the controller in the room
Time switch zone
(apartm)
4 Geographical zone of time switch
master (apartment)
Time switch zone
(room)
1 Geographical zone of time switch
master (room)
Time switch zone
(subzone)
1 Geographical zone of time switch
master (subzone)
Heat distribution
zone
2 The device forwards the heat request
to the flow temperature controller via
heat distribution zone 2
Refrigeration
distribution zone
2 The device forwards the refrigeration
request to the flow temperature con-
troller via refrigeration distribution
zone 2
6. Parameter settings on room controller 2, RXB21.1/FC-11
Settings for the zones
Path: ... > Communication
Geographical zone
(apartm)
4 Room group number
Geographical zone
(room)
2 Room number
Geographical zone
(subzone)
1 Number of the device in the room
Time switch zone
(apartm)
4 Geographical zone of time switch
master (apartment)
Time switch zone
(room)
1 Geographical zone of time switch
master (room)
Time switch zone
(subzone)
1 Geographical zone of time switch
master (subzone)
Heat distribution
zone
2 The device forwards the heat request
to the flow temperature controller via
heat distribution zone 2
Refrigeration
distribution zone
2 The device forwards the refrigeration
request to the flow temperature cont-
roller via refrigeration distribution
zone 2
Outside tempera-
ture zone
1 The device receives the outside tem-
perature from the RMB via outside
temperature zone 1