Parameter Setting Function Remarks
4. Parameter settings on the central control unit RMB795B
Basic settings
Path: ... > Commissioning > Communication > Basic settings
Clock time opera-
tion
Master The device forwards the time of day
to the slave bus users
Remote setting
clock slave
Yes The master’s clock can be set from
this device
This setting does not apply since
the device operates as master
Remote reset of
fault
Yes Faults of other bus users can be
acknowledged and reset from this
device
Settings for room group 1
Path: ... > Commissioning > Communication > Room group 1
Geographical zone
(apartm)
4 The device distributes the time pro-
gram in geographical zone 4
QAW operation
zone (apartm)
---- If a QAW740 room unit is used, its
geographical zone can be set here
Holidays / special
day operation
Autonomous Information about holidays and spe-
cial days is not distributed in the
holidays / special day zone
The setting is to be made in room
group 1 via menu Holidays / special
days. The setting has an effect on
the time program. The device dis-
tributes the time program to the
RDG of the same geographical
zone
Settings for the distribution zones
Path: ... > Commissioning > Communication > Distribution zones
Outside tempera-
ture zone
1 The device forwards the outside
temperature via outside temperature
zone 1
5. Parameter settings on room thermostat 1, RDG100KN
Settings for the zones
Path: ... > Communication
P82 - geographical
zone (apartm)
4 Room group number
P83 - geographical
zone (room)
1 Room number Consecutive numbering 1-x when
there are several RDG in the same
room group
P84 - heat distribu-
tion zone
2 The device forwards the heat re-
quest to the flow temperature cont-
roller via heat distribution zone 2
P85 - refrigeration
distribution zone
2 The device forwards the refrigeration
request to the flow temperature cont-
roller via refrigeration distribution
zone 2
6. Parameter settings on room thermostat 2, RDG100KN
Settings for the zones
Path: ... > Communication
P82 - geographical
zone (apartm)
4 Room group number
P83 - geographical
zone (room)
2 Room number Consecutive numbering 1-x when
there are several RDG in the same
room group
P84 - heat distribu-
tion zone
2 The device forwards the heat request
to the flow temperature controller via
heat distribution zone 2
P85 - refrigeration
distribution zone
2 The device forwards the refrigeration
request to the flow temperature cont-
roller via refrigeration distribution
zone 2