Parameter Setting Function Remarks
5. Parameter settings on room thermostat 2, RDG100KN
Settings for the zones
Path: ... > Communication
P82 - geographical
zone (apartm)
3 Room group number
P83 - geographical
zone (room)
2 Room number Consecutive numbering 1-x when
there are several RDG in the same
room group
P84 - heat distribu-
tion zone
1 The device forwards the heat request
to the RMH via heat distribution zone 1
P85 - refrigeration
distribution zone
1 The device forwards the refrigeration
request to the RMS via refrigeration
distribution zone 1