User Manual

44
Parameter Setting Function Remarks
5. Parameter settings on room thermostat 1, RDG100KN
Settings for the zones
Path: ... > Communication
P82 - geographical
zone (apartm)
4 Room group number
P83 - geographical
zone (room)
1 Room number Consecutive numbering 1-x when
there are several RDG in the same
room group
P84 - heat distribu-
tion zone
2 The device forwards the heat request
to the flow temperature controller via
heat distribution zone 2
P85 - refrigeration
distribution zone
2 The device forwards the refrigeration
request to the flow temperature cont-
roller via refrigeration distribution
zone 2
6. Parameter settings on room thermostat 2, RDG100KN
Settings for the zones
Path: ... > Communication
P82 - geographical
zone (apartm)
4 Room group number
P83 - geographical
zone (room)
2 Room number Consecutive numbering 1-x when
there are several RDG in the same
room group
P84 - heat distribu-
tion zone
2 The device forwards the heat request
to the flow temperature controller via
heat distribution zone 2
P85 - refrigeration
distribution zone
2 The device forwards the refrigeration
request to the flow temperature cont-
roller via refrigeration distribution
zone 2