Parameter settings
for communication
Parameter Setting Function Remarks
1. Parameter settings on the heating controller, RMH760B, basic type H4-0
Basic settings
Path: ... > Commissioning > Communication > Basic settings
Clock time opera-
tion
Slave The device receives the time of day
from the master
Remote setting
clock slave
Yes The master’s clock can be set from
this device
Remote reset of
fault
Yes Faults of other bus users can be
acknowledged and reset from this
device
Settings for the distribution zones
Path: ... > Commissioning > Communication > Distribution zones
Heat distribution
zone
1 The device receives the heat de-
mand via heat distribution zone 1
Outside tempera-
ture zone
1 The device receives the outside tem-
perature via outside temperature
zone 1
2. Parameter settings on flow temperature controller RMH760B, basic type H2-0
Basic settings
Path: ... > Commissioning > Communication > Basic settings
Clock time opera-
tion
Slave The device receives the time of day
from the master
Remote setting
clock slave
Yes The master’s clock can be set from
this device
Remote reset of
fault
Yes Faults of other bus users can be
acknowledged and reset from this
device
Settings for the distribution zones
Path: ... > Commissioning > Communication > Distribution zones
Heat distribution
zone
----
Heat distribution
zone source side
1 The device forwards the heat re-
quest to the heating controller via
heat distribution zone 1
Heat distribution
zone consumer
side
2 The device receives the heat de-
mand from both RMU via heat distri-
bution zone 2
Outside tempera-
ture zone
1 The device receives the outside
temperature via outside temperature
zone 1
3. Parameter settings on supply air temperature controller 1, RMU710B, basic type A
Basic settings
Path: ... > Commissioning > Communication > Basic settings
Clock time opera-
tion
Master The device forwards the time of day
to the slave bus users
Remote setting
clock slave
Yes The master’s clock can be set from
this device
This setting does not apply since
the device operates as master
Remote reset of
fault
Yes Faults of other bus users can be
acknowledged and reset from this
device
Settings for the room
Path: ... > Commissioning > Communication > Room
Geographical zone
(apartm)
3 The device distributes the time pro-
gram in geographical zone 3
Time switch slave
(apartm)
---- This device is the time switch mas-
ter, therefore no setting
Time switch opera-
tion
Master The device forwards the time pro-
gram to the slave bus users