Parameter Setting Function Remarks
Settings for holidays/special days
Path: ... > Commissioning > Communication > Holidays/special days
Holidays / special
day operation
Master The device forwards the information
about holidays and special days to all
slave bus users in the same holidays
/ special day zone
Holidays / special
day zone
1 The device sends the information
about holidays and special days in
holidays / special day zone 1
Settings for the distribution zones
Path: ... > Commissioning > Communication > Distribution zones
Outside tempera-
ture zone
1 The device receives the outside tem-
perature via outside temperature
zone 1
Heat distribution
zone
2 The device forwards the heat request
to the primary controller via heat
distribution zone 2
4. Parameter settings on supply air temperature controller 2, RMU710B, basic type A
Basic settings
Path: ... > Commissioning > Communication > Basic settings
Clock time opera-
tion
Slave The device receives the time of day
from the master
Remote setting
clock slave
Yes The master’s clock can be set from
this device
Remote reset of
fault
Yes Faults of other bus users can be
acknowledged and reset from this
device
Settings for the room
Path: ... > Commissioning > Communication > Room
Geographical zone
(apartm)
---- Room group number This device is a time switch slave,
therefore no setting
Time switch slave
(apartm)
3 The device receives the time pro-
gram from geographical zone 3
Time switch opera-
tion
Slave The device receives the time pro-
gram from the time switch operation
master
Settings for holidays / special days
Path: ... > Commissioning > Communication > Holidays / special days
Holidays / special
day operation
Slave The information about holidays and
special days is received by the mas-
ter
Holidays / special
day zone
1 The information about holidays and
special days is received in holiday /
special day zone 1
Settings for the distribution zones
Path: ... > Commissioning > Communication > Distribution zones
Outside tempera-
ture zone
1 The device receives the outside tem-
perature via outside temperature
zone 1
Heat distribution
zone
2 The device forwards the heat request
to the primary controller via heat
distribution zone 2