Room usage scenarios
For living rooms in retirement and nursing homes following usage scenarios are supposed to be probable:
HVAC This could be a possible HVAC scenario:
In the cold season the room temperature is increased at 6.00 – controlled by a time schedule
– to the Precomfort temperature setpoint (20 °C) and reduced again at 21.00 to the Economy
temperature level (18 °C). Also, when people enter the room, the temperature is increased to
the Comfort level (21 °C) and reduced again when people leave.
In the warm season the room temperature will be hold on the Comfort temperature setpoint
(24 °C). When the room is not occupied the temperature will be increased to the Precomfort
level (28 °C).
Lighting This could be a possible light scenario:
People manually switch on the lights via the push buttons. After a certain time after they
have left the room, all lights are automatically turned off. The lighting groups are dimmed
according to the natural light contribution to maintain a constant brightness level in the room
when occupied.
Shading This could be a possible blind scenario:
The blinds are controlled automatically. However, manual operation will be possible at any
time. When the sun rises all blinds are raised automatically. When the sun shines on the
facade, the blinds are driven to a certain position to protect people from excessive solar irra-
diance by maintaining comfortable lighting conditions in the room. After sunset, the blinds are
automatically lowered.
Control of HVAC, blinds and lighting
Control of room
HVAC
3
1
9
1
S
1
3
Y1
D3
B1
T
YR
N1T
TE0002 DG1 HQ
Floor or radiator heating and chilled ceiling
· Heating and cooling
· On/off or DC control of heating and cooling actuators
· Automatic or manual heating/cooling changeover