Data Sheet for Product
Siemens
Smart Infrastructure – Building Products
–3–
usa.siemens.com/fire
Networking | Range Data
COMMUNICATION
PROTOCOL:
Loop technology
supervised
signaling line circuit,
power limited
STORAGE
TEMPERATURE
RANGE:
-
22° –
+
140°F
(
-
30° –
+
60°C)
OPERATING
TEMPERATURE
RANGE:
+
32° –
+
120°F
(0° –
+
49°C)
RELATIVE
HUMIDITY:
5 – 85%
(non-freezing,
condensing
at low temperature)
Physical Properties
COLOR:
Carrier: RAL 9017
CAGE COVER:
Transparent
CAGE:
RAL 9017
FACEPLATE:
White
WEIGHT:
1 Lb. (454 g.)
DIMENSIONS:
{W –x– H –x– D}
4’’ –x– 4.7’’ –x– 1.2’’
(12 cm. –x– 12 cm. –x– 3.1 cm.)
Electrical Ratings
VOLTAGE RATING:
12 – 32 VDC
MAXIMUM VOLTAGE:
(for module using
communication loop)
32 VDC
OPERATING RATING:
(quiescent)
1mA
PEAK CURRENT:
1.92mA, max.
MONITORING VOLTAGE:
3VDC
CABLE-LENGTH
INPUT:
200 feet
(61 meters),
max.
INPUT-SHIELDING,
CABLE-LENGTH RANGE:
30 feet – 200 feet
(9.14m – 61m)
C
LINE-TO-LINE:
0.02 µF, max.
C
LINE-TO-SHIELD:
0.04 µF, max.
LINE SIZES
AMERICAN WIRE
GAUGE (AWG) :
14 AWG, max.
18 AWG, min.
AC Relay Output Ratings
OUTPUT
A, B, C, D
OUTPUT
B, C
OUTPUT
C
4 –x– 5
Amps max.
or 2 –x– 7
Amps
or 1 –x– 8
Amps
4 –x– 3
Amps max.
or 2 –x– 4
Amps
or 1 –x– 5
Amps
4 –x– 2
Amps max.
or 2 –x– 2.5
Amps
or 1 –x– 3
Amps
Normally Open (N.O.) – or –
Normally Closed (N.C.) Closed
Contacts
30 VDC, resistive;
125 VAC, resistive
Ambient Temp:
77°F (25°C)
30 VDC, resistive;
125 VAC, resistive
Ambient Temp:
100°F (38°C)
30 VDC, resistive or
inductive (0.35pF);
120 VAC, resistive
Ambient Temp:
120°F (49°C)
NOTES:
▪ AC output ratings are only applicable to Model
FDCIO422 interface modules that have
Engineering State (ES) version `10’ or higher.
▪ The part number (S54322-F4-A1) for Model
FDCIO422 is found on the back of each interface
module, and the ES version is placed just the right
of the part number (See illustration).
▪ Refer to Installation Operation Manual, IOM:
A6V10324662, for further details.
MODEL
OR TYPE
PART
NUMBER
PRODUCT
FDCIO422
S54322-F4-A1
Four (4)
Input / Four (4)
Output Interface
Module
FDCIO422-EOL
S54312-F7-A1
End-of-Line
(EOL) Resistor
{100 Ω
±
1% ½ W}
TB-EOL
S54322-F4-A2
TB - EOL
Terminal
Optional Accessories
[orderable through Randl Industries, Inc.]
PART NUMBER
PRODUCT
M-411000
4─
11
/
16
-Inch [12 cm.]
adapter plate
T55017
5-Inch [12.7 cm.]
back box
T55018
5-Inch [12.7 cm.]
back box
T55019
5-Inch [12.7 cm.]
back box
Product Compatibilities
MODEL OR
TYPE
DATA
SHEET
PANEL
XLS
6300
FireFinder
(fire-system overview)
XLSV
6340
FireFinder
(fire w/ voice system overview)
CERBERUS
PRO
MODULAR
8300
Cerberus PRO Modular
(overview)
FC901
9813
Cerberus PRO
50-point addressable
FC922
9815
Cerberus PRO 252-point
addressable (fire)
FC924
Cerberus PRO 504-point
addressable (fire)
FV922
9821
Cerberus PRO 252-point
addressable
(fire w/ Intelligent Voice
Communication [IVC])
FV924
Cerberus PRO 504-point
addressable
(fire w/ Intelligent Voice
Communication [IVC])
Supervised Switch Ratings
Details for Ordering
For Model FDCIO422
NOTICE
AC ratings must not be used with modules
with an ES less than 10.
The ES number can be found on the label:
ES
NOTES:
▪ Verify control panel supports Class-X mode for
FDCIO422 module of ES30 or higher.
• Class X mode must be used with FDCIO422,
modules that have Engineering State (ES)
version ’30’ or higher.