Data Sheet for Product
Siemens 
Smart Infrastructure – Building Products 
–3– 
usa.siemens.com/fire 
Networking | Range Data
COMMUNICATION 
PROTOCOL: 
Loop technology 
supervised 
signaling line circuit,  
power limited 
STORAGE 
TEMPERATURE 
RANGE: 
-
22° – 
+
140°F 
(
-
30° – 
+
60°C) 
OPERATING 
TEMPERATURE 
RANGE: 
+
32° – 
+
120°F 
(0° – 
+
49°C) 
RELATIVE 
HUMIDITY: 
5 – 85%  
(non-freezing,  
condensing 
at low temperature) 
Physical Properties 
COLOR: 
Carrier: RAL 9017 
CAGE COVER: 
Transparent 
CAGE: 
RAL 9017 
FACEPLATE: 
White 
WEIGHT: 
1 Lb (454 g.) 
DIMENSIONS: 
{W –x– H –x– D} 
4’’ –x– 4.7’’ –x– 1.2’’ 
(12 cm. –x– 12 cm. –x– 3.1 cm.) 
Electrical Ratings 
VOLTAGE RATING: 
12 – 32 VDC 
MAXIMUM VOLTAGE:  
(for module using  
FCnet communication) 
32 VDC 
OPERATING RATING: 
(quiescent) 
1mA 
PEAK CURRENT: 
1.92mA, max. 
MONITORING VOLTAGE: 
3VDC 
CABLE-LENGTH 
INPUT: 
200 feet 
(61 meters), 
max. 
INPUT-SHIELDING, 
CABLE-LENGTH RANGE: 
30 feet – 200 feet 
(9.14m – 61m) 
C
 LINE-TO-LINE: 
0.02 µF, max. 
C
 LINE-TO-SHIELD:
0.04 µF, max. 
LINE SIZES 
AMERICAN WIRE 
GAUGE (AWG) : 
14 AWG, max. 
18 AWG, min. 
AC Relay Output Ratings 
OUTPUT 
A, B, C, D 
OUTPUT 
B, C 
OUTPUT 
C 
4 –x– 5 
Amps max. 
or 2 –x– 7 
Amps 
or 1 –x– 8 
Amps 
4 –x– 3 
Amps max. 
or 2 –x– 4 
Amps 
or 1 –x– 5 
Amps 
4 –x– 2 
Amps max. 
or 2 –x– 2.5 
Amps 
or 1 –x– 3 
Amps 
Normally Open (N.O.)  or 
Normally Closed (N.C.) Contacts 
30 VDC, resistive;  
125 VAC, resistive 
Ambient Temp:  
77°F (25°C) 
30 VDC, resistive; 
125 VAC, resistive 
Ambient Temp:  
100°F (38°C) 
30 VDC, resistive or 
inductive (0.35pF); 
120 VAC, resistive 
Ambient Temp:  
120°F (49°C) 
NOTES: 
▪ AC output ratings are only applicable to Model 
FDCIO422  interface  modules  that  have 
Engineering State (ES) version ’10’ or higher. 
▪ The  part  number  (S54322-F4-A1)  for  Model 
FDCIO422  is  found  on  the  back  of  each 
interface module, and the ES version is placed 
just  the  right  of  the  part  number.  (See 
illustration). 
▪ Refer  to  Installation  Operation  Manual,   
IOM:  A6V10324662,  for  further  details.
MODEL 
OR TYPE 
PART 
NUMBER 
PRODUCT 
FDCIO422 
S54322-F4-A1 
Four (4)  
Input / Four (4) 
Output Interface 
Module 
FDCIO422-EOL 
S54312-F7-A1 
End-of-Line 
(EOL) Resistor  
{100 Ω 
±
1% ½ W} 
TB-EOL 
S54322-F4-A2 
TB - EOL 
Terminal 
Optional Accessories 
[orderable through Randl Industries, Inc.] 
PART NUMBER 
PRODUCT 
M-411000 
4─
11
/
16
-Inch [12 cm.] 
adapter plate 
T55017 
5-Inch [12.7 cm.] 
back box 
T55018 
5-Inch [12.7 cm.] 
back box 
T55019 
5-Inch [12.7 cm.]  
back box 
Product Compatibilities 
MODEL OR 
TYPE 
DATA 
SHEET 
PANEL 
XLS 
6300 
FireFinder 
(fire-system overview) 
XLSV 
6340 
FireFinder 
(fire w/ voice system overview) 
DESIGO 
MODULAR 
7300 
Desigo Modular (overview) 
FC2005 
6813 
Desigo Fire Safety 
50-point addressable 
FC2025 
6815 
Desigo Fire Safety 252-
point addressable (fire) 
FC2050 
Desigo Fire Safety 504-
point addressable (fire) 
FV2025 
6821 
Desigo Fire Safety 252-
point addressable 
(fire w/ Intelligent Voice 
Communication [IVC]) 
FV2050 
Desigo Fire Safety 504-
point addressable 
(fire w/ Intelligent Voice 
Communication [IVC]) 
Supervised Switch Ratings 
Details for Ordering 
  For Model FDCIO422 
NOTICE 
AC ratings must not be used with modules 
with an ES less than 10.  
The ES number can be found on the label:  
 ES 
NOTES: 
▪ Verify control panel  supports Class-X mode for 
FDCIO422 module of ES30 or higher. 
•  Class  X  mode  must  be  used  with  FDCIO422, 
modules  that  have  Engineering  State  (ES) 
version ’30’ or higher. 