TC Compact Unitary Equipment Controller BACnet Protocol Implementation Conformance Statement A6V10637226 2017-08-21 Building Technologies
BACnet Protocol Implementation Conformance Statement BACnet Protocol Implementation Conformance Statement Products Product Model Number Protocol Revision Software Revision Firmware Revision TC Unitary Equipment Controller, 16 point, BACnet MS/TP FLN, Rooftop Model TC16.3-UCMR.T 135-2008 N/A 3.3.1 3.4 3.5 TC Unitary Equipment Controller, 16 point, BACnet MS/TP TC16.3-UCM.T 135-2008 N/A 3.2.5 3.3.1 3.4 3.5 TC Unitary Equipment Controller, 24 point, BACnet MS/TP FLN, Rooftop Model TC24.3-UCMR.
BACnet Protocol Implementation Conformance Statement BACnet Smart Sensor (B-SS) Supported BACnet Interoperability Building Block (BIBBs) BIBB Name Initiate Execute Data Sharing • DS-RP-A Data Sharing-ReadProperty-A DS-RP-B Data Sharing-ReadProperty-B DS-RPM-A Data Sharing-ReadPropertyMultiple-A DS-RPM-B Data Sharing-ReadPropertyMultiple-B DS-WP-A Data Sharing-WriteProperty-A DS-WP-B Data Sharing-WriteProperty-B • DS-WPM-B Data Sharing-WritePropertyMultiple-B • DS-COV-A Data Sharing-C
BACnet Protocol Implementation Conformance Statement DM-DOB-B Device Management-Dynamic Object Binding-B • DM-DDC-B Device Management-DeviceCommunicationControl-B • DM-PT-A Device Management-Private Transfer-A DM-PT-B Device Management-Private Transfer-B DM-TM-A Device Management-Text Message-A DM-TM-B Device Management-Text Message-B • DM-TS-B Device Management-TimeSynchronization-B • DM-RD-B Device Management-ReinitializeDevice-B • DM-BR-B Device Management-Backup and Restore-B •
BACnet Protocol Implementation Conformance Statement Present_Value Yes Yes R Description Yes Yes O Device_Type Yes O Status_Flags Yes R Event_State Yes R Reliability Yes Out_Of_Service Yes Yes R Units Yes Yes R Resolution Yes COV_Increment Yes Time_Delay Yes - Alarm Notification Class Yes - Alarm Yes O High_Limit Yes - Alarm Yes O Low_Limit Yes - Alarm Yes O Deadband Yes - Alarm O Limit_Enable Yes - Alarm O Event_Enable Yes - Alarm Acked_Transitions Yes
BACnet Protocol Implementation Conformance Statement Deadband Yes - Alarm O Limit_Enable Yes - Alarm O Event_Enable Yes - Alarm Acked_Transitions Yes - Alarm O Notify_Type Yes - Alarm O Event_Time_Stamps Yes - Alarm O Yes O Analog Value Object Type Property_Identifier Supported Writable Object_Identifier Yes R Object_Name Yes R Object_Type Yes R Present_Value Yes Yes R Description Yes Yes O Status_Flags Yes R Event_State Yes R Reliability Yes O Out_Of_Service
BACnet Protocol Implementation Conformance Statement Polarity Yes R Inactive_Text Yes O Active_Text Yes Elapsed_Active_Time Yes Time_Of_Active_Time_Reset Yes Time_Delay Yes - Alarm Notification Class Yes - Alarm Alarm_Value Yes - Alarm Event_Enable Yes - Alarm Acked_Transitions Yes - Alarm O Notify_Type Yes - Alarm O Event_Time_Stamps Yes - Alarm O O Yes O O O Yes O O Yes O Binary Output Object Type Property_Identifier Supported Writable Object_Identifier Yes R Obje
BACnet Protocol Implementation Conformance Statement Present_Value Yes Yes R Description Yes Yes O Status_Flags Yes R Event_State Yes R Reliability Yes O Out_Of_Service Yes R Inactive_Text Yes O Active_Text Yes O Elapsed_Active_Time Yes Time_Of_Active_Time_Reset Yes O Priority_Array Yes O Relinquish_default Yes O Time_Delay Yes - Alarm O Notification Class Yes - Alarm Alarm_Value Yes - Alarm Event_Enable Yes - Alarm Acked_Transitions Yes - Alarm O Notify_Typ
BACnet Protocol Implementation Conformance Statement Object_Type Yes R System_Status Yes R Vendor_Name Yes R Vendor_Identifier Yes R Model_Name Yes R Firmware_Revision Yes R Application_Software_Version Yes R Location Yes O Description Yes O Protocol_Version Yes R Protocol_Revision Yes R Protocol_Services_Supported Yes R Protocol_Object_Types_Supported Yes R Object_List Yes R Max_APDU_Lenght_Accepted Yes R Segmentation_Supported Yes R Max_Segments_Supported
BACnet Protocol Implementation Conformance Statement Event_Time_Stamps Yes R File Object Type Property_Identifier Supported Writable Object_Identifier Yes R Object_Name Yes R Object_Type Yes R Description Yes O File_Type Yes R File_Size Yes Modification_Date Yes Archive Yes Read_only Yes R File_Access_Method Yes R Yes Required \ Optional R R Yes W Multi-state Output Object Type Property_Identifier Supported Writable Object_Identifier Yes R Object_Name Yes R Ob
BACnet Protocol Implementation Conformance Statement Description Yes Status_Flags Yes Yes R Event_State Yes R Reliability Yes O Out_Of_Service Yes Number_Of_States Yes R State_Text Yes O Priority_Array Yes O Relinquish_default Yes O Time_Delay Yes - Alarm O Notification Class Yes - Alarm Alarm_Values Yes - Alarm O Fault_Values Yes - Alarm O Event_Enable Yes - Alarm Acked_Transitions Yes - Alarm O Notify_Type Yes - Alarm O Event_Time_Stamps Yes - Alarm O Yes
BACnet Protocol Implementation Conformance Statement Trend Log Object Type Property_Identifier Supported Writable Object_Identifier Yes R Object_Name Yes R Object_Type Yes Description Yes Yes O Log_Enable Yes Yes W Start_Time Yes Yes O Stop_Time Yes Yes O Log_DeviceObjectProperty Yes O Log_Interval Yes O Client_COV_Interval Yes O Stop_When_Full Yes Buffer_Size Yes Log_Buffer Yes Record_Count Yes Total_Record_Count Yes Notification_Threshold Yes - Alarm Record
BACnet Protocol Implementation Conformance Statement Able to recieve segmented messages Yes Window Size: 32 Device Address Binding Is Static Device Binding supported? Yes Networking Options Router, Clause 6 BACnet/IP (Annex J) to BACnet MS/TP Annex H.3, BACnet Tunneling Router over UDP/IP BACnet/IP Broadcast Management Device (BBMD) Does the BBMD support registrations by Foreign Devices? Character Sets • ANSI X3.
Issued by Siemens Industry, Inc. Building Technologies Division 1000 Deerfield Pkwy Buffalo Grove IL 60089 Tel. +1 847-215-1000 Document ID A6V10637226 Edition 2017-08-21 © Siemens Industry, Inc., 2017 Technical specifications and availability subject to change without notice.