Operating instructions

Building Technologies - 14 - TEL50.GSM
5. Technical data
Power supply 10…30 VDC stabilized (230VAC +10 -15% 50-60Hz with supplied power supply)
Average consumption In operation: 700mA @ 12VDC
On stand-by: 60mA @ 12VDC
LED indicator lamps
- Power supply present
- GSM field present
- Status of alarm input
- Status of relay outputs (2)
Alarm input Potential-free and normally open (factory setting) or normally closed (selectable)
Temperature sensor input LG-Ni1000
Length of temp. sensor connections 50 m max with 1.5 mm
2
cable
Control outputs (2) Potential-free contact relay 250V AC 3A
Protection rating IP42 when correctly installed
Operating temperature 0…50°C
Operating humidity 20…90% R.H. without condensation
Dimensions 139 mm x 98 mm x 40 mm
compliant
Health and Safety (Art. 3.1 a) EN60950:2000
EMC (Art. 3.1 b) EN 301489-7 v1.1.1 (09/2000)
RF spectrum efficiency (Art. 3.2) (3-2000) EN 301419-1 v4.1.1 incl. EN 301511 v7.0.1 (12/2000)