Data Sheet for Product

s Industry, Inc.
Building Technologies Division
2–
Product Overview (continued)
Every Model TXR-320 FACP ships complete as a
black enclosure with door, durable key-lock and
available space to mount up to 12AH batteries.
Model TXR-320 FACP is compatibility listed with
Siemens Model HI121, OH121, OP121 conventional
detectors, which each utilize the standard Model DB-11
detector base.
Each Model TXR-320 FACP is
UL 864 9
th
Edition
Listed by Underwriters’ Laboratories, and is CSFM
(
#
7165-0067:0270) Approved.
Specifications
There are six (6) ‘Class B [‘Style B’] input circuits to
every Model TXR-320 Pre-Action / Deluge / Agent-
Releasing FACP. Input circuits 1 4 can be configured
as follows: Non-Verified Alarm; Non-Latching
Supervisory, Latching Supervisory or Agent Release /
Water Flow, based on the selected operation mode.
Meanwhile, input circuits 5, 6 can be programmed as
follows: Manual Release Input, Abort Input or Abort /
Manual Release Combination Input, depending on
the designated operating mode.
Output signals can be configured for ‘steady’ (fixed) or
‘escalating’ (tone changes as input operation changes).
Circuits 3 and 4 the panel’s output circuits can be
configured as any of the following: Silenceable signal,
Silenceable strobe, Non-Silenceable strobe, or
Releasing circuit.
Relay contacts are configurable for the following
system commands: common Alarm {which cannot be
disconnected}; auxiliary Alarm {disconnection capable},
common Supervisory, and common Trouble.
Note : Common Supervisory command can be converted for a
common Alarm event, provided no Supervisory input is used.
Cross zoning is an optional feature to each Model TXR-
320 FACP. For cross-zone monitoring, Inputs 1 and 2
are active zones on Output 3, while Inputs 3 and 4 are
active zones on Output 4.
Optional Modules
Model TICAC
TICAC `Class A’, Input-Circuit Converter Module
Model TICAC converts six (6) `Class B [`Style B] inputs
on each Model TXR-320 to `Class A [‘Style D’] circuits.
Wire leads are used on Model TICAC for connection to
Model TXR-320s main board. Model TICAC mounts to
the right of the main-board initiating circuits, which use
`Class B’ [`Style B’] wiring, and includes a built-in end-
of-line (EOL) resistor.
Model TOCAC
TOCAC `Class A’, Output-Circuit ConverterModule
Model TOCAC converts four (4) `Class B’ [`Style Y’]
output circuits on Model TXR-320 FACPs to two (2)
`Class A’ [`Style Z’] circuits. Every Model TOCAC is
equipped with wire leads to establish connection with
Model TXR-320’s main board. Model TOCAC mounts
to the right of the main-board indicating circuits.
Model TRM-306
TRM-306 Relay-Circuit Adder Module
Model TRM-306 provides six (6) `Form C,’ configurable
relay circuits, rated @ 28 VDC, 1A (resistive).
Each Model TRM-306 `Form C’ circuit can be configured
as a normally open (N.O.) or normally closed (N.C.)
contact. Additionally, each `Form Crelay is equipped
with a LED, which will illuminate when the relay is
energized. The relays can be configured as relay-per-
zone (1-to-1); common on Alarm; common on
Supervisory, or programmable for logical or adjacent-
zone configuration.
An adjacent-zone configuration will turn on the closest
zone when the configured zone is active. A chaining
configuration allows multiple relays to duly function.
Model TCFG-300
TCFG-300 Configuration Tool
The configuration tool (Model TCFG-300) plugs into the
main board of every Model TXR-320 FACP, offering a (2)
two-line by 20-character LCD. Model TCFG-300
configures Model TXR-320 LED-version FACPs and push
buttons on the main board.