Data Sheet for Product

s Industry, Inc.
Building Technologies Division
–3–
Specifications
Optional Modules (cont.’d)
TCFG-300 Configuration Tool
In configuration mode, the disconnect buttons for
initiating and indicating circuits act as function keys.
Removing the zone labels reveals the programming
function buttons.
Model TCFG-300 is used only for configuration
purposes only (not for normal operation).
Model TPR-300
TPR-300 City-Tie / Reverse-Polarity Module
Model TPR-300 provides outputs for city-tie box and
reverse-polarity applications. As a city-tie module,
Model TPR-300 serves as an interface between the
FACPs indicating circuits and a master box.
Model TPR-300 also provides off-premises signal
transmission for systems that must comply with NFPA
requirements for auxiliary protective systems.
As a reverse-polarity module, Model TPR-300 provides
an interface between Model TXR-320 and a reverse-
polarity receiver.
TRAM-208 Remote LED Annunciator
The Model TRAM-208 remote LED annunciator offers
eight (8) points of LED annunciation. Model TRAM-208
comes standard with bi-color LEDs that are
automatically configured for either Alarm (RED) or
Supervisory (AMBER).
Model TRAM-208 also has indicators for alternating-
current (AC) Oncommon Trouble as well as signal
silence and controls for system reset, lamp test, fire
drill, buzzer silence and signal silence. Model TRAM-
208 also allows for the control switches to be disabled
on a per-function basis.
Model TSRM-312
TSRM-312 Smart Relay Module
Model TSRM-312 provides 12 `Form C,’ configurable
relay circuits, rated @ 28 VDC, 1A (resistive). Each
circuit, which can be configured as a N.O or N.C
contact, is equipped with a LED that will illuminate
when the relay is energized.
TSRM-312 Smart Relay Module (continued)
The relays can be configured as relay-per-zone
(1-to-1); common on Alarm; common on
Supervisory, or programmable for logical or
adjacent-zone configuration.
An adjacent-zone configuration will turn on the
closest zone when the configured zone is active.
A chaining configuration allows
multiple relays to duly function.
Model TSRM-312 is DIP-switch configurable,
and connects to the RS485 bus.
Model AW-1
AW-1 Abort Station
The Abort Station (Model AW-1) uses a momentary,
N.O or N.C contact ‘Dead Man’-type push-button switch,
which while held in for activating prevents any
unintended agent discharge from the releasing circuit.
Model MH-501
MH-501 Manual Release Station
The Manual Release Station (Model MH-501) is a
double-action station that contains one (1) N.O contact.
Model MH-501 is intended for use with Siemens – Fire
Safety low-voltage systems, but has a rating of 120VAC
for connection to other systems.
Model MH-501 is constructed of durable, molded
polycarbonate material – matte-finished in red with
raised lettering in white. The housing incorporates a
push-in’ tab, which must be initially operated, thus
permitting access to the ‘pull-down’ lever.
When operated, the lever in turn locks into position
after releasing a spring-loaded contact switch. Restoring
the system to Normal can only be done by opening the
cover of the hinged housing with the reset key, followed
by closing and immediately locking the cover.
Model MH-501 is constructed with a molded housing,
fitted with a ‘pull-downlever and a push-intab.