Data Sheet for Product

s Industry, Inc.
Building Technologies Division
–4–
Compatibility with Detection Devices
Model HI121 Model OH121 Model OP121
HI121, OH121 and OP121 Conventional Detectors
The Model TXR-320 FACP is compatible (and agency
listed) for use with Siemens Model HI121, OH121 and
OP121 conventional detectors, which each utilize the
standard Model DB-11 detector base.
Model HI121 is a thermal detector that comes with a
magnet-test feature, allowing testing without the use
of a heat gun, and thus providing quick testing for
installers and test personnel to prove the integrity of
the wiring and proper connection to the FACP.
Model OH121 is a photo / thermal smoke detector that
contains a thermal sensor, which when used an
Alarm event will occur when the ambient temperature
surpasses 135°F (57.2°C), and locks the FACP into
Alarm mode.
Model OP121 is a photoelectric smoke detector with
microprocessor-controlled, self-diagnostic circuitry,
and thus eliminates the need for burdensome
sensitivity test equipment. Tri-colored LEDs (GREEN,
YELLOW and RED) serve as system-status indicators for
all three (3) conventional detectors.
Related Documentation
Product
Data Sheet
Number
Abort Station, Manual Release Station 6632
HI121 Thermal Heat Detector 6186
OH121 Photo Thermal Smoke Detector 6192
OP121 Photoelectric Smoke Detector 6193
Model DB-11 Detector Base 6161
Technical Data
Primary Power
Supply:
Primary Input Voltage:
Maximum Primary
Input Current: 1.7 Amps
Primary Input Voltage:
Maximum Primary
Input Current: 0.85 Amp.
Technical Data – (continued)
Battery
Properties:
Base cabinet accommodates a
12AH battery set
Larger batteries
require separate enclosures
Battery fuse on main module
10A micro (slow-blow) fuse
Four-Wire
Smoke Power:
300mA @ 22.3VDC, max.
Supervised
Auxiliary Power:
500mA @ 22.3VDC, max.
Manual Release
Delay:
0 30 seconds
increments of 5 seconds
Release Timer
Properties:
0 60 seconds
increments of 5 seconds
Soak Timer
Properties:
0 15 minutes
21 intervals
Details for Ordering
Model
Part
Number
Description
TXR-320 500-537020
Six (6) Zone
Deluge / Extinguishing FACP
Optional Modules | Accessories
Model
Part
Number
Description
TRAM-208 500-337019 8-Point LED Annunciator
MH-501 500-622543
Dual-Action, Agent-Release
Manual Pull Station
EL-320 500-637032
End-of-Line [EOL] with
diode (solenoids)
C
LR
-
1500
500
-
637033
C
urrent Limiter EOL Device
EL-300C 500-645852 EOL Device Plate
TCFG-300 500-737017
Custom-Configuration
Software Tool
AW
-
1
500
-
822500B
G
Abort Station
TSRM-312 500-637018 Smart Relay Module
TRM-306 500-837022 Relay Adder Qty. Six (6)
TPR
-
300
500
-
837024
City
-
Tie / Reverse Polarity Line
TICAC 500-837025
Six (6) `Class A Input Converter
TOCAC 500-837026
Two (2)
`Class A’ Output Converter
H
I
121
S54372
-
F3
-
A1
Thermal Heat Detector
OH121 S54372-F2-A1 Photo Thermal Smoke Detector
OP121 S54372-F1-A1 Photoelectric Smoke Detector
DB-11 500-094151 Detector Base
DB-3S 595-381804 Detector Base