INSTALLATION, OPERATION AND MAINTENANCE MANUAL Surge Protection Devices FSPD, TPS4 03, TPS4 09, TPS4 11 usa.siemens.
FSPD, TPS4 03, TPS4 09, TPS4 11 TPS4 03, TPS4 09, TPS4 11 Installation Instructions DANGER Hazardous Voltage Will cause death or serious injury.
FSPD, TPS4 03, TPS4 09, TPS4 11 Unpacking and Preliminary Inspection Inspect the entire shipping container for damage or signs of mishandling. Remove the packing materials and further inspect the unit for any obvious shipping damages. If any damage was found and is a result of shipping or handling, immediately file a claim with the shipping company and contact Siemens customer support. Storage Environment This SPD should be stored in a clean, dry environment.
FSPD, TPS4 03, TPS4 09, TPS4 11 TPS4 09 Catalog Logic Catalog No.
FSPD, TPS4 03, TPS4 09, TPS4 11 Pre-Installation and Installation Planning Operating Environment The standard unit uses a NEMA 4X enclosure. Flush-mount kits are available as options. Before installing, ensure that your enclosure type and application are appropriate with regard to moisture, dirt, excessive dust, flammable materials or atmospheres, corrosive vapors, etc. Please consult factory if enclosure needs to be changed.
FSPD, TPS4 03, TPS4 09, TPS4 11 Retro-fit Into Existing Panel with No Available Breaker Positions Follow all applicable Codes: Consider consolidating loads in a manner that might free breaker positions. A ten foot tap rule in NEC® 240.21(B)(1) allows you to tap the bus as long as the tap conductors are rated at least 10% of the ampacity of the panel. In the case where the ampacity of the panel is larger than the wires of the SPD, consider tapping the bus per NEC® 240.
FSPD, TPS4 03, TPS4 09, TPS4 11 Operation LED Operation Each SPD contains 1 green LED per phase shown in the appropriate voltage configuration. When the LEDs are green complete protection is present. Upon MOV stack failure the LED corresponding to the failed mode will extinguish. Audible Alarm Similar to the LEDs the Audible Alarm will sound upon suppression element failure. The Audible Alarm may be silenced by removing power (where applicable) to the SPD.
Legal Manufacturer Siemens Industry, Inc. 3617 Parkway Ln Peachtree Corners, GA 30092 United States of America Telephone: +1 (800) 333-7421 www.usa.siemens.com/spd Order No. RPIM-SPDS4-0822 © 2022 by Siemens Industry, Inc. Siemens does not make representations, warranties, or assurances as to the accuracy or completeness of the content contained herein.