Installation Instructions

3
WIRING ENTERING OUTLET BOX
Power Limited Wiring
All power limited wiring must enter the outlet box
separately from the electric light, power, Class 1, or
non-powered limited fire protection signaling conduc-
tors. For the TRI-R, wiring to terminal block positions
1, 2, 3, 4, and 5 must enter the outlet box separately
from terminals 6, 7, and 8.
IMPORTANT:
Minimize the length of wire entering the outlet box.
WIRING AT THE TERMINAL BLOCKS
Power Limited Wiring (Refer to Figure 5)
Wiring to positions 1, 2, 3, 4, and 5 is power limited.
Non-Power Limited Wiring
Wiring to positions 6, 7, and 8 is considered non-
power limited.
Note: Remove all slack from these wires by pulling
excess wiring back through the holes.
WIRES CONNECTED TO TERMINALS
1 THROUGH 5 TO ENTER/EXIT
ELECTRICAL BOX OPPOSITE SIDE
FROM WIRES CONNECTED TO
TERMINALS 6 THROUGH 8.
P
P
P
P
P
N
N
N
P = POWER LIMITED
N = NON-POWER LIMITED
Figure 5
TRI-R Power Limited Wiring
+
+
_
_
TO NEXT
ADDRESSABLE DEVICE
END OF LINE DEVICE
SEE NOTE 2
GROUND
SEE NOTES 6 AND 7
PROGRAMMABLE
RELAY CONTACTS
SEE NOTE 5
PROGRAMMABLE
SUPERVISED SWITCH
SEE NOTES 1 AND 3
FROM MXL CONTROL PANEL
OR FROM PREVIOUS
ADDRESSABLE DEVICE
Figure 8
Model TRI-D Wiring
Figure 7
Model TRI-S Wiring
NOT USED
+
+
_
_
TO NEXT
ADDRESSABLE DEVICE
END OF LINE DEVICE
SEE NOTE 2
GROUND
SEE NOTES 6 AND 7
PROGRAMMABLE
SUPERVISED SWITCH
SEE NOTES 1 AND 3
FROM MXL CONTROL PANEL
OR FROM PREVIOUS
ADDRESSABLE DEVICE
S1
S2
NOT USED
+
+
_
_
TO NEXT
ADDRESSABLE DEVICE
END OF LINE DEVICE
SEE NOTE 2
END OF LINE DEVICE
SEE NOTE 2
GROUND
SEE NOTES 6 AND 7
PROGRAMMABLE
SUPERVISED SWITCH
SEE NOTES 1, 3, AND 4
PROGRAMMABLE
SUPERVISED SWITCH
SEE NOTES 1, 3, AND 4
FROM MXL CONTROL PANEL
OR FROM PREVIOUS
ADDRESSABLE DEVICE
NOTES:
1. All supervised switches must be held closed and/or
open for at least a quarter of a second to guarantee
detection.
2. Use ULI listed EOL Model EL-30/31 mounting plate
with 470 ohm,
1
/4W resistor, P/N 140-820164. Order
Model EL-30/31 separately.
Figure 6
Model TRI-R Wiring
EOL of line device must be a 470 ohm, 1/4W
resistor. When replacing an existing TRI on
a device loop, you must also replace the
EOL resistor if it is not 470 ohms, 1/4W.
POSITIVE AND NEGATIVE
GROUND FAULT DETECTED
AT <40K OHMS FOR
TERMINALS 3,4.
POSITIVE AND NEGATIVE
GROUND FAULT DETECTED
AT <40K OHMS FOR
TERMINALS 3,4.
POSITIVE AND NEGATIVE
GROUND FAULT DETECTED
AT <40K OHMS FOR
TERMINALS 3,4 AND 6,7.
3. The supervised switches have the following ratings:
Voltage maximum: 27 VDC
Current maximum: 6mA during polling
Contact resistance maximum: 10 ohms
Maximum cable length: 200 feet (18 AWG) max
or 2.8 ohms max
C
Line to line
: 0.02uF
C
Line to shield
: 0.04uF
Max line size: 14 AWG
Min line size: 18 AWG