Installation Instructions

Figure 9
Mounting the TRI-S/-R/-D
MOUNTING SLOTS
FOR 4 INCH SQUARE
ELECTRICAL BOX
MOUNTING
HOLES FOR
SWITCHPLATE
MOUNTING SLOTS
FOR 4 DOUBLEGANG
ELECTRICAL BOX
TRI-S/-D/-R
MODULE
P/N 315-049481-5
4. Supervised switch S1 is on the first programmed
address, and Supervised switch S2 is on the second
programmed address.
5. Relay contacts are rated: 4A, 125 VAC resistive
4A, 30 VDC resistive
Inductive: 3.5A, 120 VAC (0.6P.F.)
3.0A, 30 VDC (0.6 P.F.)
2.0A, 120 VAC (0.4 P.F.)
2.0A, 120 VAC (0.35 P.F.)
2.0A, 30 VDC (0.35 P.F.)
The relay is shown in supervisory condition.
CAUTION
Ground shield wire ONLY at the specified
location on the Control Panel.
6. If a Good Local Earth Ground is Available:
a. Terminal 5 must be connected to earth ground.
b. Use wire nuts to pass the shield wire through the
electrical box with NO connection to the device
terminal block or to local ground.
c. Use shielded wire to connect the switch wiring to
the TRI.
d. Tie the switch wiring shield to the ALD wiring
shield. Do not connect shield to terminal 5 or the
local earth ground.
7. If a Good Local Earth Ground is NOT Available:
Connect shield to terminal 5.
8. If ALD wiring is not shielded, the switch wiring must
be in metal raceway.
9. In supervisory:
TRI-S/-R draws 1.8mA
TRI-D draws 2.3mA
IMPORTANT
Terminal 5 of the TRI-S/-D/-R must be connected
to a known good
earth ground for
proper operation.
If the electrical box the TRI is installed in is
grounded, connect Terminal 5 to same.
MOUNTING
Addressable Interface Models TRI-S, TRI-D, and TRI-R
mount directly into a (user supplied) double gang or 4
inch square electrical box. Fasten the module to the
square box with the switchplate using the 2 screws
provided.
NOTE: Be sure to program the TRI before fastening
the switchplate to the unit.