Data Sheet for Product
s Industry, Inc. 
Building Technologies Division 
Fire Safety 
8 Fernwood Road 
Florham Park, NJ 07932 
Tel: (973) 593-2600 
FAX: (908) 547-6877 
URL: www.usa.Siemens.com/Fire 
(SII-FS)
Printed in U.S.A.
Fire Safety 
2 Kenview Boulevard 
Brampton, Ontario 
L6T 5E4 / Canada 
Tel: (905) 799-9937 
FAX: (905) 799-9858 
July 2012 
Supersedes sheet dated 5/06 
(Rev.1) 
  Notice
: This marketing data sheet is not intended to be used for system design or installation purposes. 
  For the most up-to-date information, refer to each product’s installation instructions.
Details for Ordering 
Shipping Weight
Model 
Number
Part 
Number
Description 
Oz.  Kg. 
TRI-D 500-896226
Dual-
Input Intelli
g
ent 
Interface Module 
7 0.2 
TRI-R 500-896224
Single-
Input [w/ relay] 
Intelligent Interface 
Module 
7 0.2 
TRI-S 500-896225
Single-
Input 
Intelligent Interface 
Module 
7 0.2 
Mounting Diagram 
Specifications ─ (continued) 
The microcomputer chip for the Model TR
I-series of 
devices has the capacity of storing 
─ in memory ─ 
identification information as well as important 
operating status information. 
Siemens
 ─ Fire Safety innovative technology allows 
all Model TR
I-series intelligent interface modules to 
be programmed and tested, via Model DPU or the 
FP
I-32 Programmer / Tester. Each of these 
programmer / testers is a compact, portable and 
menu-driven accessory that makes programming 
and testing an interface device faster, easier and 
more dependable than previous methods. 
Model DPU or the FP
I-32 eliminates the need for 
mechanical addressing mechanisms (such as: 
program jumpers, D
IP switches, or rotary dials), 
since either programmer / tester device 
electronically sets the address of the Model TR
I-
series into the interface’s microcomputer-chip, non-
volatile memory. Vibration, corrosion and other 
conditions that deteriorate mechanical addressing 
mechanisms are no longer a cause for concern. 
The Model TR
I-series of intelligent interface 
modules is fitted with screw terminals for 
connection to an addressable circuit, and is fully 
compatible on the same circuit with all intelligent 
Model FP; Model 
IL and Model ID-60-series 
detectors; Model MS
I Series addressable manual 
stations, or any other addressable intelligent 
modules, such as Model CZM or Model 
ICP. 
All Model TR
I-series intelligent interface modules 
are 
UL and  ULC Listed. 
Electrical Ratings 
Current Draw: 
[Active or Standby] 
1.5mA 
Model TRI-R Relay Ratings: 
Resistive: 
4A, 125VAC 
4A, 30VDC 
Inductive: 
3.5A, 120VAC [0.6 P.F] 
3.0A, 30VDC [0.6 P.F] 
2.0A, 120VAC [0.4 P.F] 
2.0A, 120VAC [0.35 P.F] 
2.0A, 120VAC [0.35 P.F] 