User Manual

Siemens Data Sheet 6198
Building Technologies Division usa.siemens.com/fire
Product Overview
The Siemens
Fire Safety Intelligent Test Switch Module (Model TSM-1X) is a key-
activated
(T-45), addressable normally open (N.O.) momentary switch with a tri-
color
light-emitting diode (LED) indicator. The tri-
color LED mimics the status of the
associated
Siemens smoke detector or compatible device(s). Each Model TSM-1X
switch
can be configured to test and monitor group of devices, using one (1) address
on the
fire-alarm control panel (FACP) loop.
Model TSM
-1X provides a valid test of a Siemens duct detector even the detectors
found in inconspicuous, inaccessible areas
and will test associated logic functions
of duct housings and other modules. Other common applications include: fan
-
restart switch; drill switch; recall switch, and remote Arm/Disarm switch.
N
OTE: Refer to installation manual: P/N A6V101055486 to ensure Model TSM-1X
compatibility with the Siemens FACPs intended for use in the given application.
Overall, Model TSM
-1X is an economical solution since each X-
series Test Switch
seamlessly provides
combined, pre-packaged functionality of Siemens In/Out
modules (TR
I-S); Siemens status indicators (ILED-series), and T-45 test switches.
Therefore, there is no longer the need of having to buy individual parts and
configuring them in the field. Addition
ally, Model TSM-
1X is modernized through its
capability to provide built
-in isolation, which shows the location of a short.
Specifications
Model TSM
-1X is designed for
use with addressable duct detectors or other intelligent
devices on a Device Loop
Circuit (DLC) of Siemens compatible Fire A
larm Control
Panels (FACP). Turn
-key activation
will cause all associated logic functions to be
tested. Typical applications in which key activation is used include: intelligent duct
detectors | hidden or inaccessible smoke detectors | Fan, Recall, Restart, Drill and
remote Arm/Disarm switches. This alarm
condition will cause all logic associated with
the duct detector to activate. The TSM
-1X is mounted in a 3.5-inch
(8.9 cm.) deep
single
-gang back box, which is supplied-by-others (BO).
Mod
el TSM-1X supports two (2) operation methods:
Polarity insensitive mode
Isolator mode
The module can be wired in either mode and configured by the
compatible Siemens FACP.
While in isolation, the built in dual
isolators will w
ork at both sides of the module to isolate a line
short in front or behind the modu
le.
Model TSM
-1X provides intelligent built-in, dual isolation,
meeting Class X (Style 7) survivability requirements for shorts
while providing reliable alarm communication
to the Siemens
FA
CP. Additionally, Model TSM-1X allows up to 190 isolators per
loop, and up to 30 devices between isolators (wired in polarity
insensitive mode). The devices between isolators can either be
pre
-existing `H’-series or later `X’ generation devices.
Peripheral and Detection Devices
Initiating Device
Intelligent Test Switch and Status Indicator
Model TSM-1X
Architect & Engineer Specifications
Intelligent test-switch module with
momentary, normally open (N.O.)
turn-key activated (T45) switch
Dual, built-in isolators
Meets Class X (Style 7)
survivability requirements
Multi-color light-emitting diode
(LED) indicates system status:
- G
REEN | AMBER | RED
Low current draw
Restriction of Hazardous
Substances (RoHS) compliant
Mounts in a single-gang box:
- 3.5 inches (8.9 cm.) deep
Device Programmer / Tester
(Model DPU) programs and
verifies device’s address:
- programming capabilities include
testing a duct detector, as well as
other Siemens addressable devices
Capability of being installed
anywhere on a communication loop,
or on the wiring of that loop
UL864 | UL2572 | UL2017 Listed;
CAN/ULC-S527 & CAN/ULC-S576 Listed
- File S24304, Vol. 3
Model TSM-1X
Duct Detector Test Switch