Operating Instructions

13/54
Siemens TX-I/O™ Module system Functions and operation CM110561en_08
Building Technologies Digital input functions 2018-10-25
The signal is read at regular intervals and debounced on hardware level
An additional debounce time is available: 0…25.5 s (default = 0 s)
Pulses of more than 20 ms from pushbuttons are registered and kept ready for
polling
Desigo XWORKS plus: Only D20 (N/O) is available. Inversion (D20R, N/C) must
be realized via inverting in the parameterization.
P-Bus BIM : The configuration (D20. D20R) sets the contact type (N/O or N/C)
The meaning of the I/O status LED can be parameterized (TXM1.8D only):
Normal = green (default) / Alarm = Red / Service = Yellow.
The signal operation can be selected: Contact_NO (default), Contact_NC)
As a result
The I/O status LED is activated.
The process value is communicated over the bus
The LCD is activated
Digital inputs cannot be overridden locally. The override button has no effect, and if an
attempt is made to operate it, an error is displayed.
The I/O status LED shows the source signal
The LCD panel (if available) shows the source signal type (status contact, N/O or
N/C contact) and the state of the contact:
N/O contact /
N/C contact
Process value island bus
Process value
LCD-Display
I/O status LED
closed
open
active
inactive
10561z155
ON
OFF
N/O
N/C
> 20 ms
200 ms
P-Bus Polling
N/O
> 20 ms
Diagram: Cause and effect
For details, especially in relation to flashing pattern and errors: refer to the section "Dis-
play, operation and diagnostics" in the TX-I/O™ Engineering and installation guide [6].
Local override
Display