Operating Instructions

14/54
Siemens TX-I/O™ Module system Functions and operation CM110561en_08
Building Technologies Digital input functions 2018-10-25
3.2 Status indication, pulse contact
(BI Pulse NO / D20S)
(Function for P-bus BIM: See section 3.3)
Used for the acquisition of status pulses from volt-free pulse contacts and electronic
pulse transmitters such as transistors and optocouplers.
The pulses can be triggered by:
Mains voltage monitoring systems
Emergency pushbutton signals, e.g. in elevators
Start-up monitoring for analysis of faults
The function requires one I/O point
LCD
Signal Processing
(D20S)
Memory
Process
value
Acknowledge
I/O status LED
NO Contact
BUS
BUS
10561z156
Block diagram of function
The signal is read and debounced on hardware level
An additional debounce time is available: 0…25.5 s (default = 0 s)
The pulse is then saved and transmitted to the bus master
The bus master acknowledges receipt (Acknowledge)
The memory is cleared, the LED goes off, and the input is ready for a new pulse
Additional incoming pulses before the Acknowledge are ignored.
The signal operation can be selected: Contact_NO (default), Contact_NC)
Digital inputs cannot be overridden locally. The override button has no effect, and if an
attempt is made to operate it, an error is displayed.
The I/O status LED does not show the source signal, but the state of the signal
memory
The LCD panel (if available) shows the source signal type (status contact, N/O or
N/C contact)
The LCD panel shows the change (a block of 3 fields which change with each pulse):
Application
Hardware
Function
Local override
Display