Siemens TX-I/O™ Module system Functions and operation CM110561en_08
Building Technologies Digital input functions 2018-10-25
3.4 Pushbutton input (BI Push NO, BI Push NC)
Acquire potential-free button pulses (simple button/dual button).
The process values (event telegrams) are evaluated in the bus master and help to
control:
Blinds
Lighting applications
Other applications controlled by pulses
The function uses one or two I/O points (simple/dual button).
In case of a dual button, both I/O points must be located next to each other on the
same module pattern.
Only modules from series D support this function.
Signal Processing
(PBI Event)
Process values
(Events)
I/O status LED
NO Contact (UP)
BUS
10561z157
NO Contact (DOWN)
Function diagram
The signals are read and debounced on hardware level
The pulses are interpreted and converted to corresponding events.
The function then sends events at the start, the end, and partially during the pulse
(standard pulse patterns are:
Short pulse
Long pulse
Short double-click
Short/long double-click
Long double-click
Dual click (simultaneous clicking of two buttons)
The events are sent immediately on the island bus
A new event prior to sending overwrites a previous event. Exceptions:
Repeat does not overwrite start
Heartbeat (due to COVperiod) does not overwrite upcoming events
The signal operation can be selected: Contact_NO (default), Contact_NC)
Application
Hardware
Function