Operating Instructions

23/54
Siemens TX-I/O™ Module system Functions and operation CM110561en_08
Building Technologies Digital input functions 2018-10-25
Digital inputs cannot be overridden locally. The override button has no effect, and if an
attempt is made to operate it, an error is displayed.
The LED lights up in accordance with the existing signal status
Modules with an LCD panel display the source signal "Σ" (Counter), plus a block of 3
fields which change with each pulse:
N/O contact
I/O status LED
LCD display
ON
OFF
closed
open
10561D106
100 ms100 ms100 ms
N/O
Diagram: Cause and effect
The LEDs and LCD icons take at least 100 ms to change their state, even if the signals
have a higher frequency.
For details, especially in relation to flashing pattern and errors: refer to the section
"Display, operation and diagnostics" in the TX-I/O™ Engineering and installation guide
[6].
In the event of a communication failure the counter function is maintained.
The counter values
continue to be accumulated
are indicated by LED
periodically buffered
only if Power Up = Last Value
immediately after communication failure, and then each 15 min for max. 3 days
(the number of write actions on the FLASH memory are limited).
In the case of lacking module supply, the behavior depends on the configuration
value Power Up
Reset: upon the next start-up, the counter is reset to 0
Last Value: upon the next start-up, the counter is reset to the last value of the
buffer; some pulses may be lost.
When communication is restored, the bus master polls the counter reading again.
Local override
Display
Response in the
event of a fault