Operating Instructions

28/54
Siemens TX-I/O™ Module system Functions and operation CM110561en_08
Building Technologies Digital output functions 2018-10-25
Overview: behavior in case of a fault
Signal type TRA Signal type
Response in the following
cases
No address key
Powerdown
Masterdown,
integration via P-bus BIM
Response in the following case
Masterdown,
direct island bus integration
Behavior when
fault has been
cleared
BO Relay NO 250V
BO Relay NC 250V
Q250
The relays are de-energized
*)
The behavior can be parameter-
ized: the relays are de-energized,
keep the last position, or take a
parameterized state.
Automatic
operation:
operation according
to process value
Tool override or
local override:
Operation in the
same state as
before the fault (the
commanded value is
saved in the module
BO Triac NO 250V
BO Triac NC 250V
--
The Triacs are de-energized
The behavior can be parameter-
ized: the triacs are de-energized,
keep the last position, or take a
parameterized state.
BO Relay NO 250V
(Schrittschalter,
Stromstossrelais,
bistabiles Relais)
Q250
The relays are de-energized
*)
The switch status of the
power contactors is
maintained (step switch).
The behavior can be parameter-
ized, BUT: Do NOT parameterize
"Keep" or "ON", as only pulses
are needed for step switches /
bistable relays
BO Bistable NO
BO Bistable NC
--
Behavior can be parameterized, see section 5.4
BO Pulse On-Off
Q250-P /
Q250A-P
The relays are de-energized
*)
The switch status of the
power contactors is
maintained (due to self-
latching or dual coil relay)
The behavior can NOT be
parameterized,
The relays are de-energized
MO Steps
Q-Mx
The relays are de-energized
*)
The switch status of the
power contactors is
maintained by means of self-
latching.
The behavior can be parameter-
ized: the relays are de-energized,
keep the last position, or take a
parameterized state.
MO Pulse
Q250-P1…P5
The relays are de-energized
*)
The switch status of the
power contactors is
maintained by means of self-
latching.
The behavior can be parameter-
ized: the relays are de-energized,
keep the last position, or take a
parameterized state.
AO 3-Pos Relay
AO 3
-Pos Triac
Y250T
The actuator keeps its last
position.
The behavior can be parameter-
ized: the actuator goes to 0%,
keeps the last position, or goes to
a parameterized position.
BO PWM
--
The Triacs are de-energized
The behavior can be parameter-
ized: the signal goes to 0 %,
keeps the last position, or takes a
parameterized state.
BO
Blind Relay --
The relays are de-energized
The behavior can be parameter-
ized: all outputs are de-
energized, the last command is
completed, or the blind goes to a
parameterized position.
Additionally a time delay can be
set.
*) When using a normally-closed contact, a closed contact can be forced even if the
relay is de-energized.