Operating Instructions

29/54
Siemens TX-I/O™ Module system Functions and operation CM110561en_08
Building Technologies Digital output functions 2018-10-25
5.2 Maintained contact, switchover
(BO Relay NO / NC 250V / Q250)
On/off switching of a wide range of devices and loads, e.g.:
Power contactors
Relays and semi-conductor relays
Motors
Burners (control loop)
Chillers and heat pumps (control loop)
Magnetic valves
Display units and audible indicator units
Step switches, pulse switches, bistable relays
The function requires one I/O point
The TX-I/O relay modules have changeover contacts
By use of a normally-closed contact, a closed contact can be forced even if the relay
is de-energized.
Process value
I/O status LED
Relay
Active
Inactive
On
Off
10561D01
Active
Inactive
The signal operation can be selected: Relay (Default), Relay_NA
In the case of bus failure, with DC 24 V module supply available, the following backup
states van be parameterized:
No (Inactive) (= default)
Value (Active, Inactive)
Keep Same value as before the bus failure
Parameterization can be done during operation.
Pressing the override button in the middle enables/disables the local override.
The yellow override status LED indicates that local override is active
When local override is active:
Pressing "+" sets the process value to "Active"
Pressing "" sets the process value to "Inactive".
Local operation can be disabled in the configuration.
It is not admissible to couple several BOs of type Q250 to one multistate output
in the bus master. Reason: local override or each single I/O point is possible,
which may create hazardous situations. Use a multistate signal type instead,
where the outputs are electronically latched in the module.
Application
Hardware
Function
Parameterization
Local override
Warning!