Siemens TX-I/O™ Module system Functions and operation CM110561en_08
Building Technologies Digital output functions 2018-10-25
5.3 Maintained contact, triac (BO Triac NO / NC)
On/off switching of AC 24 V devices, especially:
Frequent switching (triacs do not have any problems with contact life span)
However, check the admissible switching frequency of the connected
device and adjust the parameters or the application accordingly.
Other devices with AC 24 control
silent switching
The function is supported by module type TXM1.8T only.
The function requires one I/O point.
The supply is AC 25 V, the triay closes the contact to (system ground).
Technical data (max. output of the triacs): see data sheet N8179.
Process value
I/O status LED
Relay
Active
Inactive
On
Off
10561D01
Active
Inactive
The signal operation can be selected: Triac (Default), Triac_NA
In the case of bus failure, with DC 24 V module supply available, the following backup
states van be parameterized:
No (Inactive) (= default)
Value (Active, Inactive)
Keep Same value as before the bus failure
Parameterization can be done during runtime.
The I/O status LED is ON when the triac is active, i.e. when the N/O contact is
closed and the N/C contact is open.
In the event of an error, the I/O status LED and the module status LED flash.
For details, especially in relation to flashing pattern and errors: refer to the section "Dis-
play, operation and diagnostics" in the TX-I/O™ Engineering and installation guide [6].
TXM1.8T has no local override.
The quality value "No_Output" is sent when AC 24 V is absent.
In this case the triac can not be activated the module switches the output off and
sets the process value to 0.
The fault message is only sent when a command is pending.