An additional ON or OFF pulse can be generated (e.g. by means of the local override).
Pressing one of the override buttons (n) or (n+1) in the middle enables/disables local
override
When local override is active:
Pressing "+" for one of the I/O points generates an ON command (closes relay n+1)
Pressing "" for one of the I/O points generates an OFF command (closes relay n)
The I/O status LED of I/O point "n" or "n+1" lights up concurrently with the relay
activity.
Local operation can be disabled in the configuration.
The I/O status LED is ON when the relay is active.
In the case of an error the module status LED and the I/O status LEDs assigned to
the function flash.
For details, especially in relation to flashing pattern and errors: refer to the section "Dis-
play, operation and diagnostics" in the TX-I/O™ Engineering and installation guide [6].
Local override
Display