5.8 Multistate pulse (MO Pulse / Q250-Px)
For pulse control and pulse switching of multistate loads or the associated power
contactors with self-latching for each load step.
Only one control output at a time is active.
Examples:
Fans
Pumps
Chillers
Heat pumps
The following functions can be implemented by use of external circuits (and see the
connection diagrams in the module data sheet):
If the control voltage for the self-latching circuit fails, the loads are not automatically
enabled when power is restored, even in the case of manual override. Example:
Power restoration circuit
If the bus master fails, the loads are not disabled.
Example: lighting controls
Local override on the module is possible; the contact interlock remains in effect.
With a change from automatic operation to manual override, the power contactors
retain their last switch status.
Two or more control circuits can switch the same load
(see connection diagrams in the data sheet).
Step switches, pulse switches, bistable relays: see Q250, section 5.2.
This feature covers the following signal type.
Signal type
Description
MO Pulse / Q250-Px
P-bus BIM:
Q250-P3 only
1 to n mapping only
PROFINET BIM:
Q250-P1...P4 only
Pulse, multistate with or without mutually exclusive
electronic relay interlock, depending on mapping kind
The function uses one I/O point for each switched stage plus one I/O point for
switch-off.
The I/O points must be on the same module and adjacent to each other.
I/O point number (n) is always used for the switch-off command
I/O point number (n+1) is used for the switch-on command for Stage (1), etc.
Before a stage other than 0 is operated, relay n is switched for a period equivalent to
MinOffTime, interrupting the self-latching function.
MinOffTime can be parameterized: 0.1...25.5 s (default = 0.5 s)
(P-bus BIM: MinOffTime = 1 cycle period)
The relay for the required stage is then operated for a period equivalent to PulseTime
PulseTime can be parameterized: 0.1...25.5 s (default = 0.5 s)
(P-bus BIM: 0.5...25 s)
The relays are latched.
The signal type supports 1 to n mapping only.