Product Brochure
52
Common Features
J Clamping jaw lever bypass
J 80A continuous rated
J Ground lug available
J Screw type terminals with pressure plate
J Steel or aluminum construction
J Glass filled polyester block construction
J 200% rated bypass
J Overhead and underground capabilities
J 600V rated
TYPE HQ-T TRANSFORMER-RATED METER MOUNTING EQUIPMENT
Socket Catalog Numbers Dimensions (inches) Continuous Hub Terminal Wire Range
Type Removable Handle Solid Handle L W D Ampere Rating Opening Current Term Potential Term
HQ-6T: 6 Jaw 9804-8544 9804-8548 17.5 10.0 5.0 80 RX Cl. Plate #4-14 #8-14
9804-8482 9804-8485 17.5 10.0 5.0 80 1” Hub Installed #4-14 #8-14
9804-8483 9804-8486 17.5 10.0 5.0 80 1.25” Hub Installed #4-14 #8-14
HQ-8T: 8 Jaw 9804-8542 9804-8546 17.5 10.0 5.0 80 RX Cl. Plate #4-14 #8-14
9804-8419 9804-8456 17.5 10.0 5.0 80 1” Hub Installed #4-14 #8-14
9804-8422 9804-8459 17.5 10.0 5.0 80 1.25” Hub Installed #4-14 #8-14
HQ-13T: 13 Jaw 9804-8543 9804-8547 17.5 10.0 5.0 80 RX Cl. Plate #4-14 #8-14
9804-8420 9804-8457 17.5 10.0 5.0 80 1” Hub Installed #4-14 #8-14
9804-8423 9804-8460 17.5 10.0 5.0 80 1.25” Hub Installed #4-14 #8-14
9804-8426 9804-8463 17.5 10.0 5.0 80 1.50” Hub Installed #4-14 #8-14
Consult the factory for other available options such as, but not limited to alternate
enclosure and hasp material, kearnaloxed terminals, enclosures with special KO
configurations and special labeling.
KNOCKOUTS (inches):
Capacity: 80 ampere continuous, 600 volts a.c.
Application: 6 terminal, single phase 2 or 3 wire; 8 terminal 2 or 3 phase, 3 wire, HQ-13T - 3 phase, 4 wire wye or 4 wire delta. For use
with transformer-rated Class 10 or 20 meters. May also be used on self-contained applications up to 80 ampere load.
Enclosures: Constructed of 16 gauge galvannealed steel with polyester powder coat finish. Also available in 12 gauge aluminum
upon request. All enclosures are NEMA type 3R.
Block Assembly: Glass fiber reinforced polyester. High strength, arc and track resistant.
Bypass: Lever-Operated Jaw Release - Moving lever up closes bypass, providing positive short circuiting of the current circuits and
releases jaw pressure on the meter current terminals providing easy removal of the meter. Also available is a removable
bypass handle which allows a solid cover, #37943-2 for HQ-T or #54199-2 for HQ-TS, to be placed on the box with the
bypass closed when it is necessary to remove the meter for in-shop repair or testing. Bypass capacity: 80 amp continuous.
Terminals: Set screw type with pressure plate. Current terminals will accommodate conductors from #4 to #14. Potential terminals will
accommodate from #8 to #14.
Hubs: Cover plate or single removable gasketless hubs are interchangeable.
UL: All sockets shown are UL approved.
Safety Shield: Track resistant polycarbonate transparent safety shield provides liberal insulation between potential jaws and terminals
and protection from accidental shorts and shocks.
GENERAL INFORMATION:
: 1/4
B: 1/2, 3/4
S: 1, 1-1/4, 1-1/2, 2, 2-1/2
AI: 1, 1-1/4, 1-1/2, 2, 2-1/2, 3
RX: x2.750 HUB 0P
Product Schedule 467