54
Common Features
J Clamping jaw lever bypass
J 80A continuous rated
J Ground lug available
J Screw type terminals with pressure plate
J Steel or aluminum construction
J Glass filled polyester block construction
J 200% rated bypass
J Overhead and underground capabilities
J 600V rated
J Spacing for multiple test switch configurations
TYPE HQ-TS TRANSFORMER-RATED METER MOUNTING EQUIPMENT WITH TEST SWITCH PROVISION
Socket Catalog Numbers Dimensions (inches) Continuous Hub Terminal Wire Range
Type Removable Handle Solid Handle L W D Ampere Rating Opening Current Term Potential Term
HQ-6T: 6 Jaw 9804-8557 9804-8561 19.0 13.0 5.0 80 RX Cl. Plate #4-14 #8-14
9804-8494 9804-8497 19.0 13.0 5.0 80 1” Hub Installed #4-14 #8-14
9804-8495 9804-8498 19.0 13.0 5.0 80 1.25” Hub Installed #4-14 #8-14
9804-8496 9804-8499 19.0 13.0 5.0 80 RX Opening #4-14 #8-14
HQ-8T: 8 Jaw 9804-8559 9804-8563 19.0 13.0 5.0 80 RX Cl. Plate #4-14 #8-14
9804-8518 9804-8521 19.0 13.0 5.0 80 1” Hub Installed #4-14 #8-14
9804-8519 9804-8522 19.0 13.0 5.0 80 1.25” Hub Installed #4-14 #8-14
9804-8669 9804-8523 19.0 13.0 5.0 80 RX Opening #4-14 #8-14
HQ-13T: 13 Jaw 9804-8560 9804-8564 19.0 13.0 5.0 80 RX Cl. Plate #4-14 #8-14
9804-8530 9804-8533 19.0 13.0 5.0 80 1” Hub Installed #4-14 #8-14
9804-8531 9804-8534 19.0 13.0 5.0 80 1.25” Hub Installed #4-14 #8-14
9804-8532 19.0 13.0 5.0 80 RX Opening #4-14 #8-14
Capacity: 80 ampere continuous, 600 volts a.c.
Application: HQ-6TS - Single phase, 2 or 3 wire, HQ-8TS - 2 or 3 phase, 3 wire
HQ-13TS - 3 phase, 4 wire wye or 4 wire delta
For use with transformer-rated Class 10 or Class 20 meters and appropriate meter test switch.
Enclosures: Ringless. Constructed of 16 gauge galvannealed steel with baked enamel finish for indoor or outdoor installation. Also
available in 12 gauge aluminum upon request. Box is adequately dimensioned and has mounting holes provided for test
switch installation. All enclosures are NEMA type 3R.
Block Assembly: Glass fiber reinforced polyester. High strength, arc and track resistant.
Bypass: Jaw release type. Moving lever up closes bypass providing positive short circuiting of the current circuits and releases jaw
pressure on the meter current terminals providing easy removal of the meter. Also available is a removable bypass handle
which allows a solid cover (#54199-2) to be placed on the box with the bypass closed when it is necessary to remove the
meter for in-shop repair or testing. Bypass capacity: 80 amp continuous.
Terminals: Set screw type with pressure plate. Current terminals will accommodate conductors from #4 to #14 copper or aluminum.
Potential terminals will accommodate conductors from #8 to #14 copper or aluminum.
Hubs: Available with cover plate or single removable gasketless hub. Hubs and cover plate are interchangeable.
UL: All sockets shown are UL approved.
GENERAL INFORMATION:
Consult the factory for other available options such as, but not limited to alternate
enclosure and hasp material, kearnaloxed terminals, enclosures with special KO
configurations and special labeling.
KNOCKOUTS (inches):
: 1/4
A: 1/2
AF: 1, 1-1/2, 2, 2-1/2, 3
AG: 3/4, 1, 1-1/4, 1-1/2, 2, 2-1/2, 3
RX: x2.750 HUB 0P
Product Schedule 469