5WG1205-2AB21 Touch control TC5 Application Guide A6V12035440_en--_c 2022-02-15 Smart Infrastructure
Table of Contents 1 Functions ......................................................................................... 5 2 UI description ................................................................................... 7 2.1 2.2 Home Page (Navigation function).................................................................7 Multifunction page........................................................................................9 2.2.1 Switch function...............................................
.3.6 "Page x - VRF interface & Operation" parameters and communication objects ............................................................... 72 3.3.7 "Page x - Ventilation System" parameters and communication objects ....................................................................................... 78 "Page x - Air Quality display" parameters and communication objects ....................................................................................... 86 3.3.8 3.3.9 3.3.
Functions 1 1 Functions Touch control TC5 (hereinafter refer to as TC5) is a KNX S-Mode multi-functional touch panel for display, operation and control use. The device is equipped with a 5inch color capacitance touch screen with 480 × 854 resolutions. The device is powered over KNX together with the DC 24...30 V auxiliary supply voltage. It is operated directly via touch screen. Totally up to 15 function pages and 2 home pages can be configured via ETS (ETS5.7 or later version).
1 Functions ● ● ● ● ● ● ● 6 | 121 RGB, RGBW control and color-temperature adjustment TC5 can set up dimming control page for 4 types of color lights, which are 3color RGB light, 4-color RGBW light, 4-color RGBW light optional with color temperature adjustment or brightness & color temperature adjustment. Display time, date, temperature, output day/night signal Proximity sensor, adjustment of screen brightness, buzzer Administrator function via password It is configurable.
UI description 2 Home Page (Navigation function) 2 UI description 2.1 Home Page (Navigation function) Homepages are configurable via ETS. Max. two pages, with max. eight icons per page, can be configured. The icons are associated with either pages or individual function. ● Icons associated with pages direct the end users to the desired pages by icon clicking. The associated pages can be multi-function pages for light, blind, scene, value send or single function pages such as HVAC operation pages.
2 UI description Home Page (Navigation function) Number Description ① Page setting icon. See Setting page [➙ 23], for more information. ② Date (mm-dd) and time; It can be modified on the setting page, or via object. ③ ● ● ④ 8 | 121 Icon can be configured using micro SD card. See Home page icons [➙ 115], for more details. The icon name is defined via ETS. Multiple languages are available and the name is as it’s typed. Max.
UI description 2 Multifunction page Number Description ⑤ Temperature value : If no temperature or humidity value is received, it is displayed as "---". Temperature unit (Celsius (℃) or Fahrenheit (℉)) can be configured and displayed accordingly. ⑥ : Humidity value 2.2 Multifunction page Multifunction page includes lighting, shading, scene control and sending value. Multifunction page view is configurable via ETS.
2 UI description Multifunction page 4 icons per page 6 icons per page 8 icons per page 2.2.1 Switch function The status of the switch function ● Big Icons View: There are 2 ways to indicate the light on status and this is configurable via ETS. 1. Only icon on (the right figure) indicates the lamp is on and the icon off (left picture) means the lamp is off. 2. The block and icon both on (right figure) indicates the lamp is on, and the block and icon both off (left figure) means the lamp is off.
UI description 2 Multifunction page ● List View Dragging the slider to the right indicates the function is on, and dragging the slider to the left (shown in below figure) indicates the function is off. At the same time, it can be updated and displayed according to the switch status of the bus feedback. 2.2.2 Switch/Dim function Long press the icon 500 ms to enter the dimming control page.
2 UI description Multifunction page 2.2.4 Blind function 3 kinds of blind are available: Curtain Blind, Roller shutter (without slat) and Venetian Blinds (with slat).
UI description 2 Multifunction page Number Description Number Description ① The simulation of blind position ② Sliding position in percentage ③ Up ④ Down ⑤ Stop Venetian Blinds (with slat) A6V12035440_en--_c Number Description Number Description ① The simulation of slat angle (Blind) ② ③ Sliding position in percentage ④ ● 0%: blind fully opened ● 100%: blind fully closed Louver angle in percentage ● 0%: slat in horizontal position and the light is fully in ● 100%: slat in vertical po
2 UI description General temperature control page 2.2.5 Scene recall and storage Tap the assigned scene icon (e.g. ) to send corresponding scene telegram to bus. ● ● Device can recall the scene directly by short pressing scene icon. If end user needs to change the scene setting and save changes: – Change the scene setting as desired. – Long press the scene icon until icon shakes (horizontally) and the scene change is stored to bus. – Short press the scene icon to recall the saved scene. 2.
UI description VRF air conditioner function page Fan speed change 2 Operation mode change 2.4 VRF air conditioner function page This function allows the device to act as the interface and operation unit for VRF air conditioners via a KNX to VRF gateway.
2 UI description Floor heating function page 2.5 Floor heating function page ● ● 16 | 121 Floor heating control function with 2-point or PI control according to temperature setpoint Scene and schedule functions Floor heating page in °C Floor heating page in °F Number Description Number Description ① Heating valve Open/Close indication Note: When setpoint is higher than room temperature, the valve is opened to increase the room temperature and vice versa.
UI description 2 Ventilation system function page 2.6 Ventilation system function page Ventilation system controls: ● 3-speed fan setting, opening/closing of heat recovery, filter life counting, alarm for filter change and filter life reset. ● Auto control (demand based ventilation control) via PM2.5 or CO 2 value ● Scene setting function.
2 UI description RGB dimming function page Demand based ventilation page Auto control (Demand-based PM2.5) Auto control (Demand-based CO2) 2.7 RGB dimming function page This function is for RGB or RGBW LED dimming (absolute dimming). RGBW supports color temperature, color temperature and brightness adjustment individually. 4 types of RGB dimming are available and configurable via ETS: 1. RGB: RGB light control 2. RGBW: RGBW light control 3.
UI description 2 Energy metering display function page Color temperature control RGBW+Color temperature Brightness+Color temperature Number Description Number Description ① Color temp. control ② Color temp. slider, 100K / step ③ Temp. up/down ④ Brightness bar 2.8 Energy metering display function page Energy metering display function page supports current, voltage, power and energy (electricity energy) display. Values are from bus via actuators or metering gateway.
2 UI description Air quality display function page 2.9 Air quality display function page Temperature, humidity, PM2.5, PM10, VOC, CO 2, AQI, brightness and wind speed displays can be set and these values are received from bus. Up to four items can be configured on one function page. Number Description Number Description ① Selected range ② Configured parameters The value of the configured parameter is shown as below. 20 | 121 Parameter Description Parameter Description Temperature -40...
UI description 2 Background music function page 2.10 Background music function page This function only works via the gateway which converts music control signal to KNX.
2 22 | 121 UI description Background music function page Number Description Number Description ① Blue tooth ② SD card ③ AUX audio ④ Radio FM ⑤ USB, current selection A6V12035440_en--_c
UI description Setting page 2 2.11 Setting page User can enter setting page by clicking the setting icon Note A6V12035440_en--_c on home page. Settings General home page Number Description Number Description ① Physical address ② Enable/disable button ③ Screen brightness ④ Keystroke volume KNX programming should be disabled unless professional engineers need configure the device via ETS. Proximity sensor: The screen is activated when the sensor detects that someone is approaching. 1. Off 2.
2 UI description Setting page Cleaning mode: When this mode is confirmed, the screen will be frozen within a set time. Cleaning mode Pages for date & time and system info Date & time setting page: slide date (Y, M or D) or time (H, M or S) to set Date & time setting page Timer function System info page Weekly timer - Weekly schedule function Daily schedule and weekly schedule are configurable in ETS. Weekly schedule is operational in touch screen or over bus if it’s enabled in ETS.
UI description 2 Setting page Timer settings: ● Tap icon No holiday set Holiday list: ● Timer is off during holiday.
2 UI description Screen 2.12 Screen 2.12.1 Screen saver Screen saver is configurable via ETS from the following options: ● Factory preloaded: a) Off; b) Clock; c) album (3 pictures: they are auto switched per 5 s when screen saver is activated.) Clock Album 1 Album 2 Album 3 ● Customized pictures from Micro SD card. Insert Micro SD card with the following settings: 1. Create a new folder named "picture" under the root directory of Micro SD card 2.
UI description 2 Screen Note ● ● ● Only support SDHC card and FAT32 format; Only support Micro SD cards with capacity not greater than 32 GB. The device picture storage size is approximate 4 MB. If the total size of the valid pictures in the Micro SD card is greater than 3.8 MB, message "Invalid image, please check!" pops up. 2.12.2 Theme (Wallpaper) For home page There are 3 themes available for home page:1) Dark screen (default); 2) With Siemens logo; 3) Water droplets.
2 UI description Screen Using SD card for customized themes on home page Insert Micro SD card with the following settings: 1. Save the pictures in the root directory in Micro SD card and named as "main_bg" 2. Picture resolution must be 480 * 854 and with the suffix: jpg, bmp, tjpg, png (For "png" picture, background must be opaque.) 3. New pictures take effect only when the parameter "Theme or Wallpaper" in the ETS is selected as "Default".
UI description Screen 2 Insert Micro SD card into the device, if valid pictures are detected, the following pop-up window appears. If upgrade fails, click any area outside the window to exit. Note ● ● ● Only support SDHC card and FAT32 format; Only support Micro SD cards with capacity not greater than 32 GB. The device picture storage size is approximate 4 MB. If the total size of the valid pictures in the Micro SD card is greater than 3.8 MB, message "Invalid image, please check!" pops up.
2 UI description Administrator function via password 2.13 Administrator function via password Administrator function is configurable via parameter "Admin via password" in ETS. For parameter details, see "General setting" parameters [➙ 33]. Setting page password If administrator function is enabled, a 4-digit number password is required to check or edit information in Setting page except cleaning mode. The password can be set via parameter "Set password 1 - setting icon unblocking".
UI description Administrator function via bus 2 2.14 Administrator function via bus This command is sent from bus. It can lock either whole panel (left picture) or individual function page (right picture). ● Lock whole panel: Once panel is locked, user cannot perform any operation on device while the panel is still able to receive telegrams from bus. This lock is done via object "General - Admin via bus". For object details, see "General" communication objects [➙ 37].
3 Parameters and communication objects Other pages 3 Parameters and communication objects This chapter introduces how the device is configured via ETS by setting the parameters. And the associated communication objects are introduced as well. The communication object is used to communicate with other devices via bus: ● Max. communication objects: 688 ● Max. group addresses: 2000 ● Max. associations: 2000 The number and kind of visible objects vary. All objects are never available at the same time.
Parameters and communication objects 3 "General" interface 3.1 "General" interface 3.1.1 "General setting" parameters Parameter "General setting" is used to configure language, temperature unit, screen saver, panel lock, background, etc. Name Description Range Device name (max.40 characters) Sets device name TC5 (default name) Note: This name is not displayed on TC5. It’s only visible via ETS.
Parameters and communication objects 3 "General" interface Name Description Language name Range The required language can be typed as "Language name". If Hungarian the language typed is not available in the library, English is Polish displayed. Portuguese Turkish Note: These additional languages are only available on devices with system firmware version 2.00.05 or higher.
Parameters and communication objects "General" interface … Name 3 Description Range Longitude in minutes [0'...59'] Sets longitude in minutes 0...59' Time difference from Universal Time [UTC+...
Parameters and communication objects 3 "General" interface Name Description Range Proximity sensor response function Enables or disables the use of proximity sensor Disable Enable (default) When this is enabled, a separate setting page is visible under "General". Refer to "Proximity sensor" parameters [➙ 42].
Parameters and communication objects 3 "General" interface Name Description Range Turn off backlight after [0...255] (0 = backlight never off) The time delay in seconds from the start of screen saving mode to turn off the screen backlight 0...255 s (default: 10 s) Note: "0" means the backlight is never off. It is only recommended for demonstration purpose. It shortens the product lifetime dramatically if the backlight is never off.
3 Parameters and communication objects "General" interface No. Name Object function Length Flag Data type CWT 1.024 day/night The communication object is used to modify the display time on the screen via bus. 682 General Day/Night 1 bit This communication object is used to send day/night status to the bus. The day/night state can be switched according to the time point, sunrise and sunset time or the telegram value that can be switched via bus.
Parameters and communication objects 3 "General" interface 3.1.3 "Summer time" parameters Name Description Range Summer time adjustment Sets summer time (Daylight Saving Time), options: No (default) Always Customized settings ● No: Summer time cannot be used ● Always: Summer time is always used ● Customized settings: User customized setting of summer time starts and ends The following parameters are visible when "Customized settings" is selected.
3 Parameters and communication objects "General" interface 3.1.4 "Color strip" parameters Name Description Range Color strip Defines when color strip is active Always active Note: Only active when backlight is off (default) Color strip is used to indicate: Color strip working mode ● Entering programming mode, see Parameters and communication objects [➙ 32] ● Configuration via ETS Sets operation mode of color strip Note: Color strip "permanent on" impacts the internal temp.
Parameters and communication objects "General" interface 3 Name Description Range Brightness level at nighttime Sets the brightness level of color strip at night time OFF (default), Level 1...
Parameters and communication objects 3 "General" interface 3.1.5 "Proximity sensor" parameters When human is detected during approaching or leaving sensor detection range, device sends telegram value to bus. Name Description Range Data type of output value The data type of telegram sent to bus 1bit [On/Off] 1byte [scene control] 1byte [0...255] 1byte [0...100%] Action when people approaching, The parameters define whether the telegram is sent or not when someone is approaching or leaving.
Parameters and communication objects 3 "General" interface 3.1.6 "Password" parameters This parameter is used to set password and data type sent to bus. This parameter page is enabled/disabled in "General" via parameter "Admin via password". Totally 3 passwords are allowed. Name Description Range Data type of output value The data type of telegram sent to bus 1bit [On/Off] (default) 1byte [scene control] 1byte [0...255] 1byte [0...
3 Parameters and communication objects "General" interface 3.1.7 "General sensor" parameters and communication objects Parameters for Sensors They are used to configure the internal sensor (built-in temperature sensor) and/or external sensor (sensor value over bus). The built-in temperature sensor: ● Element used is NTC100K ● The sensor locates at the bottom of the device inside the metal frame. ● Self-heating compensation in firmware with an accuracy of max.
Parameters and communication objects 3 "General" interface Name Description Range "Temp. error report" object meaning Defines the meaning of the object value 0=no error/1=error 1=no error/0=error Built-in sensor failure definition: Temperature value from ● When the temperature value exceeds the range of 20 ℃ …+ 60 ℃, it’s considered as sensor failure. ● Connection failure Determines the temperature value source for the temperature display in the homepage.
3 Parameters and communication objects "Home page" interface No. Name Object function Length Flag Data type 675 External sensor Temperature value (°C) 2 bytes CWTU 9.001 temperature (℃) The communication object is used to receive a temperature measurement value sent from a temperature sensor on bus. Range: -50...99.8 ℃ 676 External sensor Temp. error report 1 bit CRT 1.
Parameters and communication objects 3 "Home page" interface Name Description Range Description/ Headline of the page Sets the name of the home page shown on screen. Max. 15 byte text Note: Home page navigation function ● It supports multiple languages. In order to display it properly on screen, the "Codepage" should be set as "Unicode (UTF-8)". Refer to Language in display in Parameters and communication objects [➙ 32].
Parameters and communication objects 3 "Function page" interface Name Description Select page icon Range This is visible only when "Link to" is configured as the "Page Default x". This parameter links the Navigation icon on homepage to Lighting the function (page or icon) associated. Scenario ... Note: Reception Default: This option automatically selects the matched icon out of the default icons. See Home page icons [➙ 115] The default icons for homepage are icons with ID 70...73 and 75...
Parameters and communication objects "Function page" interface Name Description Range Function page 1...Function page 15 Enables or disables function page x. Totally 15 pages are configurable. Disable Enable 3 When "Function page x" is enabled, parameter "Page x" is visible and the Page x (x=1…15) can be configured.
3 Parameters and communication objects "Function page" interface 3.3.3 "Page x - Multifunction (Lighting/Blind/Scene/Value send)" parameters and communication objects Parameters Name Description Range Description/ Headline of the page Names the "Function page x". 15byte text Note: Page function ● It supports multiple languages. In order to display it properly on screen, the "Codepage" should be set as "Unicode (UTF-8)". Refer to Language in display in Parameters and communication objects [➙ 32].
Parameters and communication objects 3 "Function page" interface Name Description Range The following parameters are visible when Icon x is enabled. Select icon Determines which icon is used in display. Note: ● Default: This option automatically selects the matched icon out of the following default icons. : Switch_default (ID: 0) : Switch/Dim_default (ID: 0) Default No icon, only text Ceiling light Downlight ...
3 Parameters and communication objects "Function page" interface Communication objects Note Page number x range: 1...15, Icon number y range: 1...8 Switch No. Name Object function Length Flag Data type 1 Page x-Icon y Switching 1 bit CT 1.001 switch The communication object is used to send the on / off telegram to bus and control the on /off of the lamp. Telegram value: 0: Off 1: On 3 Page x-Icon y Status switching 1 bit CWTU 1.
Parameters and communication objects 3 "Function page" interface Send value No. Name Object function Length Flag Data type 2 Page x-Icon y Send 1bit/2bit/4bit value Send 1byte /2byte unsigned value Send 1byte percent value Send 2byte signed value 1bit on/off 2bit 0...3 4bit 0...15 1byte 0...255 1byte 0...100% 2byte 32768...32767 2byte 0...65535 CT 1.001 switch 2.001 switch control 3.007 dimming control 5.010 counter pulses (0...255) 5.001 percentage (0...100%) 8.001 pulses difference 7.
3 Parameters and communication objects "Function page" interface Roller shutter No. Name Object function Length Flag Data type 1 Page x-Icon y Up / Down 1 bit CWT 1.008 up/down The communication object is used to send a telegram value to bus to control the opening/closing of the Roller shutter. Telegram value: 0: Move up 1: Move down 2 Page x-Icon y Stop 1 bit CT 1.007 step The communication object is used to send a telegram for stopping the roller shutter movement to bus.
Parameters and communication objects 3 "Function page" interface Blind (up/down/stop) No. Name Object function Length Flag Data type 1 Page x-Icon y Up / Down 1 bit CWT 1.008 up/down The communication object is used to send a telegram value to bus to control the opening/closing of the Roller shutter. Telegram value: 0: Move up 1: Move down 2 Page x-Icon y Stop 1 bit CT 1.007 step The communication object is used to send a telegram for stopping the blind movement to bus.
3 Parameters and communication objects "Function page" interface Name Description Range Description/ Headline of the page Names the "Function page x". 15byte text Note: Page function ● It supports multiple languages. In order to display it properly on screen, the "Codepage" should be set as "Unicode (UTF-8)". Refer to Language in display in Parameters and communication objects [➙ 32].
Parameters and communication objects 3 "Function page" interface Name Weighting of internal and external value Description Range Defines the exact weighting in percentage.
Parameters and communication objects 3 "Function page" interface Name Description Range Temperature setpoint is configured in a separate page. Refer to "Temp. setpoint" parameters [➙ 63] Option: Disable The following parameter is visible when "Room operation mode" is disabled. Base setpoint (°C) Sets initial value of the temperature. The setting temperature can be modified via object "Base setpoint (°C)", the new value is stored after the bus powers off. 10.0 / 10.5 /11.0 / 11.5 / … / 34.0 / 34.
Parameters and communication objects 3 "Function page" interface No. Name Object function Length Flag Data type 162 Page x-Temp. Cntrl. (receive) Setpoint (°C), base or absolute 2 bytes CW 9.001 temperature (℃) ● Room operation is disabled, the communication object is used to modify the base value of the set temperature.
3 Parameters and communication objects "Function page" interface No. Name Object function Length Flag Data type 172 Page x-Temp. Cntrl. (receive) Fan speed auto 1 bit CWU 1.003 enable The object is used to receive status feedback from automatic fan speed control. Telegram value: 0: Cancel automatic 1: Automatic 173 Page x-Temp. Cntrl Effective setpoint (send) 2 bytes CRT 9.
Parameters and communication objects 3 "Function page" interface No. Name 181 Page x-Temp. Cntrl Fan speed low (send) Fan speed Object function Length Flag Data type 1 bit 1 byte CT 1.001 switch 5.001 percentage (0...100 %) Fan speed can send control telegrams of the fan speed to bus via four 1bit objects (objects 181,182,183,184) or one 1byte object "Fan speed".
3 Parameters and communication objects "Function page" interface 3.3.4.1 "Fan Speed" parameters Note: The following parameters are visible when "Data type of fan speed" is set as 1byte.
Parameters and communication objects 3 "Function page" interface 3.3.4.2 "Temp. setpoint" parameters Absolute setpoints Basic setpoint + setpoint shifting Note: The page is visible when "Room operation mode" is enabled. Important: All selected setpoints must be in the range configured by the parameters "Minimal possible setpoint value [5...40]" and "Maximal possible setpoint value [5...40]" on the "General Temp. Control" page (see "Page x General Temp.
Parameters and communication objects 3 "Function page" interface Name Description Range The following parameters are visible when Cooling, Heating & Cooling and Absolute setpoints are selected. Comfort mode: Setpoint cooling [5...40] Sets the setpoint of Comfort mode 5...40 °C (default: 22 °C) Standby mode: Setpoint cooling [5...40] Sets the setpoint of Standby mode 5...40 °C (default: 24 °C) Economy mode: Setpoint cooling Sets the setpoint of Economy mode [5...40] 5...
Parameters and communication objects 3 "Function page" interface Name Description Range Command Type Sets the control logic/method for Heat/Cool application. On/Off - two level control PWM - PI control switching (1 bit) Modulating - PI control continuous (8 bit) Invert control value Sets whether to invert control value in order to meet the requirement of different type of valves. No Yes The following two parameters are visible when "On/Off - two level control" is selected. Lower Hysteresis [0...
3 Parameters and communication objects "Function page" interface Name Description Range Send control value cyclically [0...255] Sets the period for cyclically sending the control value to bus. 0…255 min 3.3.5 "Page x - Enhanced Floor Heating" parameters and communication objects Parameters Assign "Page x" as single function –"Enhanced Floor Heating" page for floor heating application.
Parameters and communication objects "Function page" interface A6V12035440_en--_c 3 67 | 121
Parameters and communication objects 3 "Function page" interface Name Description Range Description/ Headline of the page Names the "Function page x". 15byte text Note: Page function ● It supports multiple languages. In order to display it properly on screen, the "Codepage" should be set as "Unicode (UTF-8)". Refer to Language in display in Parameters and communication objects [➙ 32].
Parameters and communication objects 3 "Function page" interface Name Description Range Command Type Sets the temperature control logic / method. On/Off - two level control PWM - PI control switching (1 bit) Modulating - PI control continuous (8 bit) Object value of Heating on/off Defines the triggered of floor heating on/off.
Parameters and communication objects 3 "Function page" interface Name Description Range The following parameters are visible when "Enable" is selected. Floor heating state for timer Sets the power on/off status of the floor heating interface of timer x. Temp. Setpoint [32...64] This parameter is visible when "Floor heating state for timer" 32...64 *0.5 ℃ is selected as "On". It’s to set the temperature setpoint of timer x.
Parameters and communication objects 3 "Function page" interface No. Name Object function Length Flag Data type 165 Pagex- Enhanced FH Timer enable/disable (receive) 1 bit CW 1.003 enable The communication object is used to disable/ enable the timing function of the floor heating. The disable / enable telegram value is specifically defined by the parameter. 166 Pagex- Enhanced FH Scene (receive) 1 byte CW 18.
3 Parameters and communication objects "Function page" interface 3.3.6 "Page x - VRF interface & Operation" parameters and communication objects Parameters Assign "Page x" as single function –"VRF Interface & Operation" page. It works as an interface & Operation unit for VRF air conditioning system. (VRF refers to variable Refrigerant Flow HVAC technology). To work with VRF device, it should connect with a gateway.
Parameters and communication objects 3 "Function page" interface Name Description Range Description/ Headline of the page Names the "Function page x". 15byte text Note: Page function ● It supports multiple languages. In order to display it properly on screen, the "Codepage" should be set as "Unicode (UTF-8)". Refer to Language in display in Parameters and communication objects [➙ 32].
Parameters and communication objects 3 "Function page" interface Name Description Range Data type of fan speed This parameter is for setting the data type of fan speed. 1bit 1byte These parameters are used to define different fan speed value. 0...255 It’s status feedback for fan speed. The device updates fan speed icon status according to the feedback value received.
Parameters and communication objects "Function page" interface 3 Data type of operation mode: 1byte Data type of fan speed: 1byte A6V12035440_en--_c 75 | 121
3 Parameters and communication objects "Function page" interface Communication objects Gateway_1byte Gateway_1bit Note Page number x range: 1...15 No. Name Object function Length Flag Data type 161 Page x - VRF VRF: External temperature (receive) 2 bytes CWTU 9.001 temperature (℃) The communication object is used for receiving the temperature measurement value sent by the external temperature sensor on bus and displaying the indoor temperature on the screen.
Parameters and communication objects 3 "Function page" interface No. Name Object function Length Flag Data type 167 Page x - VRF Fan mode (receive/send) 1 bit CWTU 1.003 enable This communication object is visible when the "Data type of operation mode" is 1bit. It is used to send air conditioning mode Fan control telegram and receive status feedback. 168 Page x - VRF Auto mode (receive/send) 1 bit CWTU 1.
3 Parameters and communication objects "Function page" interface 3.3.7 "Page x - Ventilation System" parameters and communication objects Parameters Assign "Page x" as single function –"Ventilation System" page.
Parameters and communication objects 3 "Function page" interface Name Description Range Description/ Headline of the page Names the "Function page x". 15byte text Note: Page function ● It supports multiple languages. In order to display it properly on screen, the "Codepage" should be set as "Unicode (UTF-8)". Refer to Language in display in Parameters and communication objects [➙ 32].
Parameters and communication objects 3 "Function page" interface Name Description Range Time delay between fan speed switching [0...100] Determines the time delay of the switching process in milliseconds. This time setting should take the technical specification of the fan into consideration. [0...100]*50ms If a value of 1…100 is chosen, proceed as follows when switching the fan speed from A to B: 1. Turn off the fan 2. Pause (time delay defined) 3. Switch to a new speed 4.
Parameters and communication objects 3 "Function page" interface Communication objects Note Page number x range: 1...15 No. Name Object function Length Flag Data type 162 Page x-Ventilation Power On/Off (receive/send) 1 bit CWTU 1.001 switch The communication object is used for sending a ventilation system control switch telegram, and can also receive the feedback of the ventilation system control status.
3 Parameters and communication objects "Function page" interface No. Name Object function Length Flag Data type 169 Page x-Ventilation Fan speed No.2 (receive/send) Status fan speed (receive) 1 bit 1 byte CWTU 5.010 percentage (0...100 %) 1.001 switch Status fan speed (receive): The communication object is visible when the fan speed type is "1byte" and is used to receive the status feedback of the fan speed.
Parameters and communication objects 3 "Function page" interface 3.3.7.1 "Auto Operation" parameters CO2 PM2.5 Note The following parameters are visible when "Auto Operation (Demand based ventilation)" is enabled. Name Description Range Object value - activate/exit auto operation Sets the telegram value to active automatic operation. 0=Activated/1=exit 1=Activated/0=exit Control via The source of the control value is used to set the automatic operation. PM2.
Parameters and communication objects 3 "Function page" interface Name Description Range Threshold for fan speed: from Low to Medium Defines the threshold for switching the fan speed to the middle fan speed, if the control value is greater than or equal to the threshold set by this parameter, then the middle fan speed is running. 1...
Parameters and communication objects "Function page" interface 3 state is maintained. Only less than 25 or greater than or equal to 45 changes the running state of the fan.
3 Parameters and communication objects "Function page" interface 3.3.8 "Page x - Air Quality display" parameters and communication objects Parameters Assign "Page x" as single function –"Air Quality Display" page. Name Description Range Description/ Headline of the page Names the "Function page x". 15byte text Page function Note: ● It supports multiple languages. In order to display it properly on screen, the "Codepage" should be set as "Unicode (UTF-8)".
Parameters and communication objects 3 "Function page" interface Name Description Range Object datatype of VOC Sets the data type of VOC Value in ug/m3 (DPT_7.001) Float value in ug/m3 (DPT_9.030) Float value in ppm (DPT_9.008) Object datatype of PM2.5 Sets the data type of PM2.5 Value in ug/m3 (DPT_7.001) Float value in ug/m3 (DPT_9.030) Object datatype of PM10 Sets the data type of PM10 Value in ug/m3 (DPT_7.001) Float value in ug/m3 (DPT_9.
3 Parameters and communication objects "Function page" interface No. Name Object function Length Flag Data type 166 Page x-Air Quality (receive) VOC (receive) 2 bytes CWTU 7.001 pulses 9.008 parts/million (ppm) 9.030 concentration (ug/m3) The communication object is used to receive the input of the VOC value and get the corresponding value from the bus to be updated to the display in mg/m3.Range: 0...9.99 mg/m3, the data type of the object is set by the parameter.
Parameters and communication objects "Function page" interface Name Description Range Description/ Headline of the page Names the "Function page x". 15byte text Page function 3 Note: ● It supports multiple languages. In order to display it properly on screen, the "Codepage" should be set as "Unicode (UTF-8)". Refer to Language in display in Parameters and communication objects [➙ 32].
3 Parameters and communication objects "Function page" interface Communication objects Note Page number x range: 1...15, energy meter number range 1...8 No. Name Object function Length Flag Data type 161 Page x-Energy Meter 1 Current in mA (DPT 7.012) 2 bytes CWTU 7.012 current (mA) The communication object is used to receive the current value from the bus and update it to the screen display. The display range is 0...65535 mA, and the resolution is 1 mA.
Parameters and communication objects "Function page" interface 3 3.3.10 "Page x - RGB Dimming" parameters and communication objects Parameters Assign "Page x" as single function –"RGB Dimming" page. Name Description Range Description/ Headline of the page Names the "Function page x". 15byte text Page function Note: ● It supports multiple languages. In order to display it properly on screen, the "Codepage" should be set as "Unicode (UTF-8)".
3 Parameters and communication objects "Function page" interface Communication objects Note Page number x range: 1...15 RGB & RGBW No. Name Object function Length 161 Page x-RGB Dimming Red dimming value 1 byte RGB dimming 3 bytes value Flag Data type CT 5.001 percentage (0...100%) 232.600 RGB value 3x (0...255) 1 byte: The communication object is used to send the brightness value of the control R (red) channel to the bus. Telegram value:0...
Parameters and communication objects 3 "Function page" interface No. Name Object function 163 Page x-RGB Dimming Blue dimming value 1 byte Length Flag Data type CT 5.001 percentage (0...100%) The communication object is used to send the brightness value of the control B (blue) channel to the bus. Telegram value: 0...100 % 164 Page x-RGB Dimming White dimming value 1 byte CWT 5.001 percentage (0...
3 Parameters and communication objects "Function page" interface 3.3.11 "Page x - Background Music" parameters and communication objects Parameters Assign "Page x" as single function –"Background Music" page. When function is enabled, the objects for background music control are visible, such as Off/On, play/pause, volume, previous song/next song, play mode, music source, etc. The music could be source from USB/SD/AUX/FM/BT. For some of the music source, a gateway is needed.
Parameters and communication objects 3 "Function page" interface Name Description Range Description/ Headline of the page Names the "Function page x". 15byte text Note: Page function ● It supports multiple languages. In order to display it properly on screen, the "Codepage" should be set as "Unicode (UTF-8)". Refer to Language in display in Parameters and communication objects [➙ 32].
3 Parameters and communication objects "Function page" interface Communication objects Page number x range: 1...15 No. Name Object function Length Flag Data type 161 Page x-BgMusic Power On/Off (receive/send) 1 bit CWTU 1.001 switch The communication object is used to send the background music on / off controlling telegram to the bus, to control the power of the background music module, and to receive feedback from the switch status of the background music on the bus.
Parameters and communication objects "Timer function" interface 3 3.4 "Timer function" interface 3.4.1 "Timer function" parameters Name Description Range Timer function This is used to set timer function. Enable Disable Timer 1...Timer 5 If Timer function is enabled, a separate page timer options appear. You can set the timer function that is used for each specific timer. Enable Disable 3.4.
Parameters and communication objects 3 "Timer function" interface Name Description Range Timer disable function This is used to determine whether to enable or disable time function via objects and the trigger value of enabling/disabling the function. Disable Weekly time configuration Triggers moment of timer x. Monday...Sunday Monday...Sunday Configures the day of a week to enable timer x.
Parameters and communication objects 3 "Event Group function" interface No. Name Object function Length Flag Data type 487 Timer 1 2byte unsigned value 2 bytes CT 7.001 pulses The communication object is used to send the preset telegram value of the time function to the bus, and the time function, default value and object type set by the parameters. The time is up to send the default telegram value to the bus. A total of 16 timing (x = 16) can be set.
3 Parameters and communication objects "Event Group function" interface Communication objects No. Name Object function Length Flag Data type 520 Event Event recall 1 byte CW 17.001 scene number This communication object triggers each output in the event group to send a specific value to the bus by recalling the scene number. Telegram: 0…63 521...528 Event Group NO.1...Event Group - NO.8 Sub event output 1...Sub event output 8 1bit 1byte 2byte CT 1.001 switch 5.010 counter pulses (0...
Parameters and communication objects "Logic function" interface 3 3.6 "Logic function" interface 3.6.1 "Logic operations" parameters Parameter setting "Logic operations" is for enabling the logic calculation. Totally up to 8 logic function can be configured. ● AND, OR and XOR ● Gate forwarding, it can turn one input into another output or multiple outputs ● Threshold comparator ● Conversions between different data types Name Description Range Logic-No.1...Logic-No.
3 Parameters and communication objects "Logic function" interface 3.6.2 "AND/OR/XOR" parameters and communication objects Parameters 102 | 121 Name Description Range Logic operation Sets the logic operation AND/OR/XOR - Input a...Input h This is used to set whether input x participates the calculation. Disconnected If yes, it defines which format is used in the calculation. Normal Inverted Default value This is used to set the default value of input x.
Parameters and communication objects "Logic function" interface 3 Communication objects No. Name Object function Length Flag Data type 585...592 Logic -No.1...Logic -No.8 Input a...Input h 1 bit CWTU 1.002 boolean The communication objects are used to receive the value of logical input Input a...Input h. 593 Logic -No.1...Logic -No.8 Logic result 1bit CT 1.002 boolean The communication object is used to send the results of logical operation. 3.6.
3 Parameters and communication objects "Logic function" interface Name Description Range Logic operation Sets the logic operation Gate forwarding - Date type of Input/Output object This is used to set the object type of input/output. 1bit 4bit 1byte Scene No. to be forwarded at startup [0...64, 0=inactive] After the device is activated, by default, it triggers the initial scene/ scenario, which is forwarded by logical gate. This is configured with parameters. 0...64 1: Gate trigger scene No.
Parameters and communication objects "Logic function" interface 3 3.6.4 "Threshold comparator" parameters and communication objects Parameters Name Description Range Logic operation Sets the logic operation Threshold comparator - Data type of output value This is used to set the data type of the threshold value. 4bit 1byte 2byte 4byte Threshold value [0...255] This is used to set threshold value. The value range is determined by the data type selected. Data type of output value = 4bit: 0...
3 Parameters and communication objects "Logic function" interface Communication objects No. Name Object function Length Flag Data type 585 Logic -No.1...Logic -No.8 Threshold value input 4 bit 1 byte 2 bytes 4 bytes CWU 3.007 Dimming control 5.010 counter pulses (0...255) 7.001 pulses 12.001 counter pulses CT 1.002 boolean The communication object is used as input value for threshold comparator. 593 Logic -No.1...Logic -No.
Parameters and communication objects "Logic function" interface 3 Communication objects 2×1Bit-->1×2Bit "2x1bit --> 1x2bit" function: converts two 1bit values to one 2bit value, such as Input bit1=1, bit0=0--> Output 2bit=2 No. Name Object function Length Flag Data type 585 Logic -No.1...Logic -No.8 Input 1bit-bit0 1 bit CWU 1.001 switch CT 2.001 switch control 586 Input 1bit-bit1 The communication object is used to input a value that needs to be converted. 593 Logic -No.1...Logic -No.
3 Parameters and communication objects "Logic function" interface 2×1Byte-->1×2Byte "2x1-byte --> 1x2-byte" function: converts two 1-byte values to one 2-byte value, such as Input 1-byte-low = 255 ($FF), Input 1-byte-high = 100 ($64) --> Output 2byte = 25855 ($64 FF) No. Name Object function Length Flag Data type 585 Logic -No.1...Logic -No.8 Input 1byte-low 1 byte CWU 5.010 counter pulses (0...255) CT 7.
Parameters and communication objects "Logic function" interface 1×2Byte-->2×1Byte 3 "1x2-byte --> 2x1-byte" function: converts one 2-byte value to two 1-byte values, such as Input 2-byte = 55500 ($D8 CC) --> Output 1-byte-low = 204 ($CC), Output 1-byte-high =216 ($D8) No. Name Object function Length Flag Data type 585 Logic -No.1...Logic -No.8 Input 2byte 2 bytes CWU 7.001 pulses CT 5.010 counter pulses (0...255) The communication object is used to input a value that needs to be converted.
3 Parameters and communication objects "Logic function" interface 3×1Byte-->1×3Byte "3x1-byte --> 1x3-byte" function: converts three 1-byte values to one 3-byte value, such as Input 1-byte-low = 150 ($96), Input 1-byte-middle = 100 ($64), Input 1byte-high = 50 ($32)--> Output 3-byte = $32 64 96 No. Name Object function Length Flag Data type 585 Logic -No.1...Logic -No.8 Input 1byte-low 1 byte CWU 5.010 counter pulses (0...255) CT 232.600 RGB value 3x(0...
Icons Functional page icons 4 4 Icons 4.1 Functional page icons A6V12035440_en--_c Replacement ID ETS options Replacement ID 4.1.
Icons 112 | 121 ETS options Replacement ID Functional page icons Replacement ID 4 ETS options 31 Party 32 Meeting 33 Sleeping 34 Reading 35 Media 36 Cleaning 37 TV 38 Audio 39 Socket (CHN) 40 Socket (EU) 41 Fan 42 Door lock 43 Door access 44 Power supply 45 Window 1 46 Window 2 47 Alarm 48 Timer 49 Projector 50 Multimedia 51 Electric heating 52 Air conditioner 1 53 Air conditioner 2 54 Fresh air 55 Setting Icon Icon A6V12035440_en--_c
Icons Functional page icons 4 4.1.2 Icon replacement for function page via Micro SD card Insert Micro SD card with the following settings: 1. Create a folder named Functionicon under the root directory in Micro SD card; 2. Put icon files in folder with the identical name of the one to be replaced. – All icons must be named following the naming rule below; – For each Icon ID number (see Icon list for function page [➙ 111]), "Off" status icon is mandatory. i.e. for ID=n icons, "icon_n_a.png" is mandatory 3.
4 Icons Functional page icons Insert Micro SD card to upload the customized icons: Insert Micro SD card to delete the customized icons: 1. Create a folder named Functionicon under the root directory in Micro SD card; 2. Do not put any icon files with correct name in folder Note 114 | 121 ● ● ● Only support SDHC card and FAT32 format; Only support Micro SD cards with capacity not greater than 32 GB. The device picture storage size is approximate 4 MB.
Icons Home page icons 4 4.2 Home page icons 70 ETS options Icon Multifunction_default Replacement ID Replacement ID 4.2.1 Icon list for home page 71 ETS options Temperature control_default e.g. 72 A6V12035440_en--_c VRF device_default No specific e.g. icon Display current settings, such as heating /cooling, fan speed, temperature 73 Floor heating_default e.g.
Icons 108 116 | 121 ETS options Current monitor Icon Replacement ID Home page icons Replacement ID 4 109 ETS options Icon Heating 110 Cooling 111 Heating / Cooling 112 Temperature 113 AV system 114 Security 115 Bedroom 1 116 Bedroom 2 117 Living room 1 118 Living room 2 119 Dining room 121 Study room 122 Gym 123 Basement 124 Office 125 Meeting room 126 Exhibition hall 127 Training room 128 Warehouse 129 Building 130 Recreation 131 Reception A6V12035440_
Icons Home page icons 4 4.2.2 Icon replacement for home page via Micro SD card Insert Micro SD card with the following settings: 1. Create a folder named Pageicon under the root directory in Micro SD card; 2. Put icon files in folder with the identical name of the one to be replaced. – All icons must be named following the naming rule below; – For each Icon ID number (see Icon list for home page [➙ 115]), "Off" status icon is mandatory. i.e. for ID=n icons, "icon_n_a.png" is mandatory 3.
4 Icons Home page icons Insert Micro SD card to delete the customized icons: 1. Create a folder named Pageicon under the root directory in Micro SD card; 2. Do not put any icon files with correct name in folder Note 118 | 121 ● ● ● Only support SDHC card and FAT32 format; Only support Micro SD cards with capacity not greater than 32 GB. The device picture storage size is approximate 4 MB. If the total size of the valid pictures in the Micro SD card is greater than 3.
Appendix Cyber security disclaimer 5 5 Appendix 5.1 Cyber security disclaimer Siemens provides a portfolio of products, solutions, systems and services that includes security functions that support the secure operation of plants, systems, machines and networks. In the field of Building Technologies, this includes building automation and control, fire safety, security management as well as physical security systems.
Issued by Siemens Switzerland Ltd Smart Infrastructure Global Headquarters Theilerstrasse 1a CH-6300 Zug +41 58 724 2424 www.siemens.com/buildingtechnologies © Siemens Switzerland Ltd, 2020 Technical specifications and availability subject to change without notice.