Commissioning Instructions
Table Of Contents
- 1 Functions
- 2 UI description
- 2.1 Home Page (Navigation function)
- 2.2 Multifunction page
- 2.3 General temperature control page
- 2.4 VRF air conditioner function page
- 2.5 Floor heating function page
- 2.6 Ventilation system function page
- 2.7 RGB dimming function page
- 2.8 Energy metering display function page
- 2.9 Air quality display function page
- 2.10 Background music function page
- 2.11 Setting page
- 2.12 Screen
- 2.13 Administrator function via password
- 2.14 Administrator function via bus
- 2.15 Other pages
- 3 Parameters and communication objects
- 3.1 "General" interface
- 3.2 "Home page" interface
- 3.3 "Function page" interface
- 3.3.1 "Page settings" parameters
- 3.3.2 "Function page" communication objects
- 3.3.3 "Page x - Multifunction (Lighting/Blind/Scene/Value send)" parameters and communication objects
- 3.3.4 "Page x - General Temp. Control" parameters and communication objects
- 3.3.5 "Page x - Enhanced Floor Heating" parameters and communication objects
- 3.3.6 "Page x - VRF interface & Operation" parameters and communication objects
- 3.3.7 "Page x - Ventilation System" parameters and communication objects
- 3.3.8 "Page x - Air Quality display" parameters and communication objects
- 3.3.9 "Page x - Energy Metering Display" parameters and communication objects
- 3.3.10 "Page x - RGB Dimming" parameters and communication objects
- 3.3.11 "Page x - Background Music" parameters and communication objects
- 3.4 "Timer function" interface
- 3.5 "Event Group function" interface
- 3.6 "Logic function" interface
- 4 Icons
- 5 Appendix
UI description
Administrator function via password
2
30 | 121
A6V12035440_en--_c
2.13 Administrator function via password
Administrator function is configurable via parameter "Admin via password" in ETS.
For parameter details, see "General setting" parameters [➙ 33].
Setting page password
If administrator function is enabled, a 4-digit number password is required to check
or edit information in Setting page except cleaning mode. The password can be set
via parameter "Set password 1 - setting icon unblocking". For parameter details,
see "Password" parameters [➙ 43].
After the setting icon is unlocked, the settings are enabled. Once leaving Settings
page by tapping the home icon , the page is automatically locked again.
Screen saver password
If administrator function is enabled, screen operation requires password after the
screen saver is on or the screen is off. The password is a 4-digit number.
Two passwords are available. They can be set via parameters "Set password 2 -
screen waking up" and "Set password 3 - screen waking up". For parameter
details, see "Password" parameters [➙ 43].