Commissioning Instructions

Table Of Contents
Parameters and communication objects
"Function page" interface
3
56 | 121
A6V12035440_en--_c
Name
Description
Range
Description/ Headline of the page
Names the "Function page x".
Note:
It supports multiple languages. In order to display it
properly on screen, the "Codepage" should be set as
"Unicode (UTF-8)". Refer to Language in display in
Parameters and communication objects [➙ 32].
Maximum 12 characters displayed for upper case letter
and 15 characters displayed for lower case letter, but
only 5 characters for Chinese, 7 characters for Russian
or Greek
15byte text
Page function
Configures the type of this function page.
Note:
Page 1...5 can only be multifunction, while page 6...15 can
be either multifunction or single functions.
Multifunction
(Lighting/Blind/Scene/Value
send);
General Temp. Control;
Enhanced Floor Heating;
VRF Interface & Operation;
Ventilation System;
Air Quality Display;
Energy Metering Display;
RGB Dimming;
Background Music.
Temperature value from
Sets the resource of the temperature reference.
Internal sensor: Built-in temperature sensor. The
configuration refers to "General sensor" parameters
and communication objects [➙ 44]
External sensor: Temperature value over bus
Internal and External sensor weighting: Using
calculated value
Internal sensor
External sensor
Internal and External sensor
weighting
The following parameters is visible when "Internal and External sensor weighting" is selected.