Commissioning Instructions

Table Of Contents
Parameters and communication objects
"Function page" interface
3
A6V12035440_en--_c
61 | 121
No.
Name
Object function
Length
Flag
Data type
181
Page x-Temp. Cntrl
(send)
Fan speed low
Fan speed
1 bit
1 byte
CT
1.001 switch
5.001 percentage
(0...100 %)
Fan speed can send control telegrams of the fan speed to bus via four 1bit objects (objects 181,182,183,184) or one 1byte
object "Fan speed".
1 bit: The corresponding fan speed is activated on the screen, and the corresponding object sends telegram "1" to the bus,
except for the telegram sending 0 of the fan speed.
1byte: The corresponding telegram value of each fan speed is defined by the parameter. Activate the corresponding fan speed
on the screen, and object 181 sends the corresponding telegram value of the fan speed to bus.
182
Page x-Temp. Cntrl
(send)
Fan speed medium
1 bit
CT
1.001 switch
The communication object sends control telegrams of the fan speed medium to bus.
183
Page x-Temp. Cntrl
(send)
Fan speed high
1 bit
CT
1.001 switch
The communication object sends control telegrams of the fan speed high to bus.
184
Page x-Temp. Cntrl
(send)
Fan speed off
1 bit
CT
1.001 switch
The communication object sends control telegrams of the fan speed off to bus.
185
Page x-Temp. Cntrl
(send)
Fan speed auto
1 bit
CT
1.003 enable
The communication object is used for sending the automatic control telegram of the fan speed to bus. Telegram value:
0: Cancel automatic
1: Automatic
186
Page x-Temp. Cntrl
(send / receive)
Power On/Off
1 bit
CWTU
1.001 switch
The communication object is used to switch and control the HVAC function of the device, and the corresponding control is
turned off when the HVAC is turned off.
187
Page x-Temp. Cntrl
(send)
Base setpoint (°C)
2 bytes
CRT
9.001 temperature
(℃)
Room operation mode is disabled, the communication object is used to send the base value of the set temperature.
Room operation is enabled and
The temperature is set to "Base setpoint + setpoint shifting", the communication object is used to send the base
value of the set temperature, i.e., the temperature setting value of Comfort mode, and the setting temperature of
Standby mode and Economy mode changes according to the relative change. In Protection mode, only the
temperature setting value of the protection mode is modified.
The temperature is set to "Absolute setpoints", the communication object is used to send the temperature setting
value of the current room operation mode.