Installation Guide

Product Specification Sheet GD30.2
Answers for industry.
General Duty Safety Switch
Type VBII, 30 Amp, 240 Volts, Type 1 (Indoor)
Standards and Ratings
UL Listed under file #E4776
Meets UL98 for switches and UL50
for enclosures
Meets NEMA Standard KS-1 for
enclosed switches
Meets NEC wire bending space
requirements
Rated 10,000 AIC with Class H fuses
or 100,000 AIC with Class R fuses
Suitable for use as service
entrance equipment
Features
• Quick-make and break
switching action
Double break visible blade design
Highly visible ON/OFF indication
Single cover interlock
Accessories
1
Use Neutral Kit for 1-phase, 3-wire or 3-phase, 4-wire applications.
2 Dual horsepower ratings:
Std - applies when non-time delay fuses are installed.
Max - applies when time-delay fuses are installed.
General Information
Catalog Number Description
W410473A Fusible Replacement Interior 3-Pole (GF321N)
W410473B Non-Fusible Replacement Interior 3-Pole (GNF321N)
Catalog Ship. Wt. (lbs.)
Number Description (Std Pkg)
GF321N 3 Phase, 4 Wire, Fusible 24 (5)
GNF321
1
3 Phase, 3 Wire, Non-Fusible 24 (5)
Replacement Parts
Catalog Number Description
GSRK60 Equipment Ground Kit (Wire Range #14-2 Cu/Al)
W410190
1
Neutral Kit
GSRK321 Class R Fuse Clip Kit
Horsepower Ratings
2
Catalog
1 Phase, 2 Wire, 240V AC 3 Phase, 3 Wire, 240V AC
250V
Number Std Max Std Max DC
GF321N 1¹⁄₂ 337¹⁄₂ 5
GNF321 3 7¹⁄₂ 5
Mechanical Lug Wire Ranges (60/75°C, Cu/Al)
Description Wire Range
Line, Load,
#14-6 AWG
Neutral
or
#14-8 AWG

Summary of content (2 pages)