ACVATIX™ 2-port and 3-port control ball valves, PN 40, with externally threaded connection VAG61.., VBG61.. For use in heating, ventilation, and air conditioning plants as control or shutoff valve. In closed circuits. • • • • • • • • Ball valve body made of brass CW602N (DZR) DN 15...50 kvs 1...63 m3/h Flat sealing, externally threaded connections G..B, as per ISO 228-1 Fitting sets ALG.. with threaded connection Rotational angle 90° Can be combined with electromotoric rotary actuators GQD..9A, GMA..9E..
Features • • • Moderately price: Optimized flow rates mean smaller ball valves can be selected. Low torque means you can combine them with small, less expensive rotary actuators. Long life expectancy: Maintenance-free construction, also thanks to low friction stem and polished ball made of chrome-plated DZR brass. Simple mounting: The brackets, premounted on the actuators, means you can mount them on the ball valves without tools.
Sizing Flow diagram: 63 40 25 16 10 6,3 2,5 1,6 1 Low noise operation 4 --- Δpmax for VAG61.. and VBG61..
211D03a Ball valve characteristic curve Through-port Flow rate kv / kvs 1 0,8 0,6 0,4 0,2 0 0 20 40 60 80 90° Rotational angle Flow characteristics 0…100 % -> A ─ AB equal percentage, ngl = 3.9 per VDI / VDE 2173 4211D02a 3-port Flow rate kv / kvs 1 0,8 0,6 0,4 0,2 0 0 20 40 60 80 90° Rotational angle Through-port 0…100 % -> A ─ AB equal percentage, ngl = 3.
Cavitation Cavitation increases wear and tear of the ball and seat and results in unwanted noise. Cavitation can be prevented by not exceeding the differential pressures as per the flow diagram and maintaining the static pressures depicted below.
Operating pressure and operating temperature Liquids: Operating pressure [bar] Operating temperature [°C] Operating pressure and medium temperature per IS0 7005 (Observe all local and applicable laws). Type summary Type Control ball valve 2-port Product no. 6 Siemens Smart Infrastructure DN Control ball valve 3-port Stock number Product no. kvs Sv [m3/h] Stock number VAG61.15-1 S55230-V100 ─ ─ 15 1.0 VAG61.15-1.6 S55230-V101 VBG61.15-1.6 S55230-V120 1.6 VAG61.15-2.
Accessories Temperature adapter ALJ100 DANGER Hazard to life for the combination ALJ100 with GMA and ASK77.2! Combining temperature adapter ALJ100 with ASK77.2 and rotary actuator GMA operated at AC 230 V ~ or rotary actuator GMA with auxiliary switch voltage AC 230 V ~ can result in life-threatening shocks if used inappropriate. ● Never combine rotary actuator GMA operated at voltage of AC 230 V ~ with temperature adapter ALJ100.
Equipment combinations Type Rotary actuators GQD..9A Δpmax GSD161.9A Δps Δpmax Δps GDB..9E.. Δps Δpmax GMA..9E.. Δpmax Δps GLD161.9E.. Δpmax Δps GLB..9E.. Δpmax GDD161.9E Δps Δpmax Δps 350 1400 ─ ─ [kPa] VAG61.15.. VAG61.20.. 350 1400 350 1400 350 1400 1400 1400 1400 1000 1000 1000 VAG61.25.. VAG61.32-10 VAG61.32-16 VAG61.32-25 350 VAG61.40-16 VAG61.40-25 ─ ─ ─ ─ ─ ─ 350 350 800 800 800 600 600 600 VAG61.40-40 VAG61.50-25 VAG61.50-40 VAG61.50-63 VBG61.15..
Overview of rotary actuators for ball valves Type 1) Product no. Operating voltage Stock number 2) BPZ:GQD131.9A GQD161.9A 2) BPZ:GQD161.9A GSD161.9A 2) S55499-D232 2) GDB341.9E 2) GQD131.9A GDB141.9E GDB161.9E Positioning 2) 2) GDB161.9E/MO Signal AC/DC 24 V 3-position A6V10636056 S55499-D200 AC/DC 24 V 2 or 3 point 150 s ─ ─ ─ S55499-D201 AC 100-240 V S55499-D275 AC/DC 24 V 0/2…10 V ─ 3-position GMA161.9E BPZ:GMA161.9E GMA161.9E/MO S55499-D683 GLD161.
Applications with auxiliary functions A standard actuator with corresponding functionality can be used if a ball valve application requires a rotary actuator with auxiliary functions (e.g. auxiliary switch or potentiometer). In this case, mounting kit ASK77.x is required in addition to the rotary actuator. Follow the mounting instructions when mounting. Rotary actuator Options Order text: Mounting kit GMA..1E Potentiometer, auxiliary switch ASK77.2 Accessory Kit BV for GMAxx1.
Engineering We recommend installing the ball valve with spring return since temperatures are lower on heating plants which increases the lifespan of the sealing gland on the stem. Ensure there is no cavitation (see Section Technical design [➙ 2]). A filter must be installed upstream of the ball valve to increase functional safety. We recommend using temperature adapter ALJ100 in locations exposed to condensation to protect the actuator.
Mounting It is easy to assemble the ball valve and rotary actuator; it can be done at the construction site. No special tools or settings required. Ball valve VAG61.. / VBG61.. is supplied together with mounting instructions M4212 (7431909220). Mounting position VAG61.. VBG61.. Pipe connection Avoid leakage: • Install fittings as per ISO 7-1. Ball valves (internal threading) = "Rp"; Piping (external threading) = "R". • Do not use too much hemp or PTFE tape. • Do not tighten pipe threading to the very end.
Maintenance Ball valves VAG61.. and VBG61.. are maintenance free. Disposal Do not dispose of the device as part of domestic waste. • Special handling of individual components may be required by law or make ecological sense. • Adhere to all local and currently applicable laws and regulations. Warranty Technical data on specific applications are valid only together with Siemens products listed under "Equipment combinations".
Technical data Functional data VAG61.. VBG61.. PN class PN 40 per ISO 7268 Operating pressure Per ISO 7005 within the permissible media temperature as per Section Technical design [➙ 2] Ball valve characteristic curve Through-port: 0…100 % Equal percentage, ngl = 3.
4212M01 Dimensions DN = Nominal size H = Total height of actuator plus minimum mounting distance to wall or ceiling, for mounting, connection, operation, maintenance, etc. H1 = Type Dimension from the pipe to the center to install actuator (upper edge) DN B C D G VAG61.15.. 15 27 VAG61.20.. 20 34 VAG61.25.. 25 VAG61.32.. 32 VAG61.40.. VAG61.50.. L1 L2 33 42 G1B 43.5 42 42 G1¼B 44.7 35 38 48 42 G1½B 59.7 42 G2B 40 49 65.7 42 50 61 81.6 42 mm H1 H2 87 27.
4212M02 DN = Nominal size H = Total height of actuator plus minimum mounting distance to wall or ceiling, for mounting, connection, operation, maintenance, etc. H1 = Type Dimension from the pipe to the center to install actuator (upper edge) DN B C C1 D mm VBG61.15.. 15 VBG61.15-6.3 G L1 Inch H1 H2 mm 27 43.5 59.5 42 G1B 43.5 87 24.2 33.7 27 44.1 61 42 G1B 44.3 88.6 27.6 37.6 VBG61.20.. 20 34 44.7 66 42 G1¼B 44.7 89.4 27.6 37.6 VBG61.25.. 25 35 49.
Fittings Type VAG61.. VBG61.. Article number Type Article number Valve type G Rp Inch Inch ALG152 BPZ:ALG152 ALG152B S55846-Z100 VAG61.15.. G1B Rp ½ ALG202 BPZ:ALG202 ALG202B S55846-Z102 VAG61.20.. G 1¼ B Rp ¾ ALG252 BPZ:ALG252 ALG252B S55846-Z104 VAG61.25.. G 1½ B Rp 1 ALG322 BPZ:ALG322 ALG322B S55846-Z106 VAG61.32.. G2B Rp 1¼ ALG402 BPZ:ALG402 ALG402B S55846-Z108 VAG61.40.. G 2¼ B Rp 1½ ALG502 BPZ:ALG502 ALG502B S55846-Z110 VAG61.50..
Revision numbers Type Type Shutoff ball valve VAG61.. Changeover ball valve VBG61.. 2-port 3-port Valid from rev. no. VAG61.15-1 ..A ─ ..A VAG61.15-1.6 ..A VBG61.15-1.6 ..A VAG61.15-2.5 ..A VBG61.15-2.5 ..A VAG61.15-4 ..A VBG61.15-4 ..A VAG61.15-6.3 ..A VBG61.15-6.3 ..A VAG61.20-4 ..A VBG61.20-4 ..A VAG61.20-6.3 ..A VBG61.20-6.3 ..A VAG61.20-10 ..A ─ ─ VAG61.25-6.3 ..A ─ ─ VAG61.25-10 ..A VBG61.25-10 ..A VAG61.25-16 ..A ─ ─ VAG61.32-10 ..A ─ ─ VAG61.