Required Checks
Branch Circuit
Ensure the branch circuit feeding the VersiCharge has no other loads connected to it.
Ensure that the VersiCharge is connected to the correct sized circuit breaker:
40 A 2-Pole Breaker for 30 A VersiCharge Units
90 A 2-Pole Breaker for 70 A VersiCharge units
*Utilizing the amperage adjustment switch does NOT allow users to de-rate the branch circuit breaker
Verify correct wire gauge is used, based on VersiCharge amperage rating, type of conductor and length of run from
supplying panel
Lugs are rated for copper conductors only
Refer to NEC® Chapter 9, Table 8 for wire size calculations
Verify that Load Center or Distribution Panel board has sufficient capacity to operate the added load of the VersiCharge
30 A devices will consume 7.2 kW of power
70 A devices will consume 16.8 kW of Power
Location
Verify that the VersiCharge is installed within the height restriction set forth in the NEC® Section 625.28
Indoor: 18 in. to 48 in. above floor level
Outdoor: 24 in. to 48 in. above parking surface
*VersiCharge in Rated NEMA 4 and can be installed indoors or outdoors
Verify that the installation is not in the presence of flammable vapors
Verify that the mounting is attached to a stud or other structure that will support the 20+ lb weight of the device
VersiCharge Inspector Checklist
Help take out the guess work when checking a Siemens VersiCharge
EVSE System for UL and NEC compliance.