Required Checks
Branch Circuit
☐ Ensure the branch circuit feeding the VersiCharge has no other loads connected to it.
☐ Ensure that the VersiCharge is connected to the correct sized circuit breaker:
☐ 40 A 2-Pole Breaker for 30 A VersiCharge Units
☐ 90 A 2-Pole Breaker for 70 A VersiCharge units
*Utilizing the amperage adjustment switch does NOT allow users to de-rate the branch circuit breaker
☐ Verify correct wire gauge is used, based on VersiCharge amperage rating, type of conductor and length of run from
supplying panel
☐ Lugs are rated for copper conductors only
☐ Refer to NEC® Chapter 9, Table 8 for wire size calculations
☐ Verify that Load Center or Distribution Panel board has sufficient capacity to operate the added load of the VersiCharge
☐ 30 A devices will consume 7.2 kW of power
☐ 70 A devices will consume 16.8 kW of Power
Location
☐ Verify that the VersiCharge is installed within the height restriction set forth in the NEC® Section 625.28
☐ Indoor: 18 in. to 48 in. above floor level
☐ Outdoor: 24 in. to 48 in. above parking surface
*VersiCharge in Rated NEMA 4 and can be installed indoors or outdoors
☐ Verify that the installation is not in the presence of flammable vapors
☐ Verify that the mounting is attached to a stud or other structure that will support the 20+ lb weight of the device
VersiCharge Inspector Checklist
Help take out the guess work when checking a Siemens VersiCharge
EVSE System for UL and NEC compliance.