Installation Guide

19 © 2014 Siemens Industry, Inc. 813776
o Disconnect the attachment plug wires from
the terminal block by loosening screws in
position 1, 2, and 3.
o Do not adjust the two screws on top of the
terminal block unit. These are for factory use
only.
o Disconnect and remove strain relief and
entire cord-and-plug assembly
§ Continue with directions in Wiring Steps for
Hard-Wired Installation’ starting at ‘Proper
strain relief is required for conduit connection’
Wiring Steps for Hard-Wired Installation
§ Open hinged cover by loosening four cover Phillips closure screws.
§ Remove barrier by removing the two securing screws.
DANGER Hazardous voltage. Will cause death or serious injury. Turn off
Power before working on this equipment by turning the circuit breaker to
which this circuit is wired to the off position.
§ Chose appropriate conduit hub depending on whether your installation is
inside or outside. Outdoor installations must be completed with a water tight
conduit hub. We recommend flexible conduit for easier use during
installation.
§ Locate a stud within the wall to attach the mounting bracket and receptacle.
For concrete or masonry walls, install appropriate anchors.
§ Verify that the stud or anchor and surrounding materials can handle the 20+
lbs load of the VersiCharge.
§ Verify local code with respect to installation height:
o Installation height is regulated by NEC®; however this can vary based on
local jurisdiction.
o NEC® 2011 specifies:
§ Indoor (NEC® Article 625.29B) = installation 18-48 inches above
ground level
§ Outdoor (NEC® Article 625.30B) = installation 24-48 inches above
ground level