Siemens Building Technologies VISONIK DCS Functions and System Messages VVS18 CM2U8567E / 04.1999
Landis & Staefa Division Function DRR 2-131
When the reaction is triggered, the VISONIK-DCS executes a specific macro command
from the macro text register (TXCM,M) ??? of the selected language at ONE defined
device. ???
Number of the macro text.
Language of the macro text register.
Output device (STA, M1..M15) at which the text is to be printed.
Print slave messages.
The VISONIK DCS normally only prints spontaneous messages if the status of a point
changes in the peripheral equipment (???).
An SLVM reaction is required in order to force point messages (e.g. cyclic polling of a
temperature using a date reaction).
When the reaction is triggered, the VISONIK DCS reports the main value of the point in
the defined message mask, without the point status having changed.
Slave messages have an exclamation mark before the timestamp in the message line.
The VISONIK DCS starts/stops one of the available DCS COLBAS tasks.
Number of the COLBAS task whose operation mode is to be modified.
Requested operation modes:
RUN Stops the COLBAS task if it is active, and starts it at the line number
entered.
RESTART Starts a COLBAS task only if it is inactive. If the task is active, the
instruction is ignored.
STOP Stops the task and prints a STOP message.
END Stops the task without a message.
Line number at which the task is to be started by a RUN or RESTART instruction.
No Reaction (MRR/GRR)
This option is only implemented for group reactions and maintenance reactions.
Group reactions (GRR) and maintenance reactions (MRR) include additional
mechanisms that do not require a special reaction section:
•
Group reactions include a device changeover mechanism for alternative or auxiliary
devices.
•
Maintenance reactions include an operating hours counter.
If reaction programs are used for such cases, the reaction entry should be set to
"Reaction=.".
Automatic picture/point selection
When the reaction PICT is triggered, the VISONIK DCS automatically displays the
selected picture in VISONIK-Insight.
The picture is only displayed if VISONIK Insight is free. Otherwise, it is saved until it is
opened manually.
Specification of the picture to be displayed.
In the case of reaction programs whose "reason" is a point change (PRR/SRR), the user
can enter an "F" in the reaction entry instead of a fixed picture number. With this entry
the picture that has been assigned to the respective "reason" address using the function
COS,PICT (???) or the function PICT will be automatically displayed.
The PICT parameter contains the number of the picture on which a given point is
displayed.
VISONIK Insight, Output device number (T1..T15)
If a printer channel is selected as graphic device, the encoded picture number will be
printed only.
Reaction MC
Macrotext number
Language
Output device
Reaction SLVM
Reaction CB
CB Task
Mode
COLBAS Line No.
Reaction .
Reaction PICT
Picture number
Graphic devices