User Manual

CM2U8567E / 04.1999 VISONIK DCS Functions and System Messages VVS18 Siemens Building Technologies
2-132 Function DRR Landis & Staefa Division
The VISONIK DCS executes the same reaction with the further addresses as with the
address defined under "Reaction =". This feature allows for reaction entries to be
economised.
The user can assign up to four different further addresses to each reaction entry,
provided the reaction is one that modifies point parameters
(Reaction =UA/TA) or prints slave messages (Reaction =SLV).
For each reaction entry, the user can use the message mask to define which output
devices of the VISONIK DCS are to register the reaction:
Message Mask =MSGDEV : ?
MSGDEV: M1
MM00: M1&M2
:
MM15: M1&M2
Message Mask =MSGDEV :
Message Mask =MSGDEV means that the reaction will be registered on the message
devices that are listed according to message priority in the parameters DSM0..DSM3
(point type SY) of the point specified under "Reaction=".
The MSGDEV mask also takes device allocations with group reactions (alternative or
auxiliary devices) into account.
2.13.3 LI, List Data Registers
The LI operation can be used to selectively list the reaction entries. The contents of the
list can be filtered according to the following criteria:
by start date
by entry numbers
by reactions
If the reaction type CT, MC or CB is entered at the prompt "Reaction=?:", the user can
make a finer selection according to text or task number.
1. further address
n. further address
Message mask