User Manual
Siemens Building Technologies VISONIK DCS Functions and System Messages VVS18 CM2U8567E / 04.1999
Landis & Staefa Division Function EDI 2-145
2.15.2.8 LINK, Join Adjacent Files
With Operation LINK only adjacent files can be linked together.
T8 13:42:46 Function=PNT : EDI,LINK
File Number=1: 5
Anzahl=0 : 3 >>okay!
=== File 5: 17.12.1998/Do 13:18:08 0 bytes (+ 3 Linkfiles!)
Files 5, 6, 7 and 8 are now linked together, i.e. file 5's length has been extended by that
of files 6, 7 and 8.
Linked files (in the above example, 6, 7 and 8) cannot be listed with LI. When copying
such linked files the required memory area must be taken into account, e.g. do not copy
three full linked files to a standard file.
If the prompt for "Number" is answered with "0" (Number = 0), then information about
those linked files following is displayed in addition to the selected file number.
T8 13:45:26 Function=PNT : EDI,LINK
File Number=1:
Number=0 : 0
File 5 linked to 3 following file(s) !
File Number=1:
2.15.2.9 UNLK, Separate Joined Files
With UNLK any linked files must be separated from lower to higher numbered files.
Files 8, 9 and 10 have been joined to file 7.
Unlinking the four files:
EDIT,UNLK,7
2.15.3 Call up of Editor from Function CB
Before the Editor can be called up from Function CB a COLBAS Task must first be
selected:
T2 15:56:45 Function =PNT : CB --> Entry into CB dialogue
TSK0 : Monitor
TSK0 : TSK14 --> Task 14 selected
TSK14 : Editor
TSK14 : EDI --> Call-up of Editor
File number =(1..250): 33 --> File 33 selected
The Editor now sets its "cursor" to the file start after which the file can be handled with
the Full Screen Editor.
The above described Operations which are selected after opening the Function EDI c a
n n o t be called from Function CB.
Remark:
Directory
Example
Note