Landis & Staefa Division Quick Guide - Working in CTRL-D mode 1-9
1.1 Working in Ctrl-D mode
The Ctrl-V mode is the same as the older version of the Ctrl-V mode. In Ctrl-D mode,
only data points of the local system can be displayed. Within a linked system, Ctrl-V
mode must be selected to select points from other systems.
Proceed as follows to start the Ctrl-D mode:
Step Procedure Comment
1
CTRL+D Start Ctrl-D mode
2
Enter and confirm data point address Technical or user address
permitted.
Delete individual characters
using the backspace key or
delete the entire address
through direct entry.
3
Enter and confirm parameter name
In Ctrl-D mode, the screen display is split. The upper half of the screen contains the
selected data point with its parameters, the lower half is used for the DCS dialogue.
Terminal operation is displayed as follows:
PAR = AI :
/Analogue Input (Measurement) /
. AI $52'020 (m9p1)
16.4 PS
DOK-Server
AI =16.4 ALsta =2=Normal Acknowledged
SERVICE - Parameter
AERSTA=0: AICMAX=157.4 AICMIN=-47.4 AIRMAX=8191: ARC =19:
ARCM =79 Ev/h: COVsta=Acknowledged&withAckn EMV =16.4 ERLST =6
ERTST =0 IDC =56=MW: MSGDEV=M3&M4 MV =16.4
MVINF =2 (2R1K ) MVSTA =ok OPLST =0=i.O OSV =No:
PCPA =HIWL PCWHEN=26.11.1998 18:13:09 PCWHY =HAND PStyp =8=BPS
QEVE =.: RITA =A:$RI1 RxTim =26.11.1998 18:19:57 SST =0=Normal
SST1 =0=Normal: TA =A:$52'020 (m9p1) TAPS =A:$52'PS TELE =0=Nein
TEVE =.: TYP =4=AI WHEN2 =0
-------------------------------------------------------- -- $52'020 (m9p1)
ctrl/D
Ctrl/E = End Function Ctrl/K = End Update.
Taste = Further Param.
How do I proceed ?