User Manual

Siemens Building Technologies VISONIK DCS Functions and System Messages VVS18 CM2U8567E / 04.1999
Landis & Staefa Division Function GRR 2-159
2.16.5 LSTA, List Reaction Register State
This provides an overview of all Reaction Registers.
T8 12:13:36 Function=PNT : GRR
Operation =CH : LSTA
Register Total Entries
--------------------------------------------------
Group Reactions GRR 1
Process Reactions PRR 7
Maintenance Reactions MRR 1
Time Reactions TRR 1
Step Reactions SRR 1
Date Reactions DRR 1
Total 12
Operation =LSTA :
2.16.6 LOCT, List Reaction Entries in Octal
The LOCT operation can be used to selectively list the reaction entries according to the
same criteria as the LI operation. The normal list is followed by a printout of the same
data in octal code.
T8 08:28:36 Function=PNT : GRR
Operation =CH : LOCT
Address Mask =* : $100*
Entry =* : *
Reaction =.. : $100'041
GRR 08:29:12 Start of D A T A - L I S T 09.08.1996/Fr
T8
$d100'040 / 5
Edge 1
Reaction PACH___Change Point Parameter
Address DO $d100'041
Parameter DO_____Set Digital Output: Priority=0
Value 0=Off
Reporting MSGDEV M1
DSW/Offset = REA. 3 / 232
0/ 100 76 5 0 4000 4 0 0
20/ 0 0 0 0 0 0 1000 100000
40/ 41 62052 1622 0 0 0 0 0
60/ 0 0 0 0 0 0 0 0
GRR 08:29:15 End of D A T A-L I S T 09.08.1996/Fr T8
The list may be required by Landis & Gyr for diagnostic purposes.