User Manual

Siemens Building Technologies VISONIK DCS Functions and System Messages VVS18 CM2U8567E / 04.1999
Landis & Staefa Division Function KEY 2-167
2.1.2.1 New Entry
To make a new "KEY" entry an authorised user has to specify the following conditions:
Operation =CH :
User Code: JB
New Entry:
----------
User Name=: John Brown
User Code=JB:
Expiry Date=31-Dec-99 ?
Expiry Date-(dd-mm-yy):
Delete Key after expiry=No: ?
Delete Key after expiry=(No ,Yes ): YES
Address Range=***'**'**"****: ?
Address Range=(UA,TA,EKL,...,...,*)
A00'A1'22"AAAA
$eee'mm'p, $eee'VPn, $eee'RGn, $eee'PLn
$eee
..=range
...=special range
*=all
: a01'b*
Flag =$0'000: ?
Flag =(UA,TA),.
A00'A1'22"AAAA
$eee'mm'p, $eee'VPn, $eee'RGn, $eee'PLn
, .: $FL77
Function Level=0: ?
Function Level=(0..5), ??: 4
Parameter Level=0: ?
Parameter Level=(0..5), ??: 3
Operating Range=Local: ?
Operating Range=(Local,Global): Local
Working Language=0: ?
Working Language=(0..2): 1
Extra Device(s) =.: ?
Extra Device(s) =(.,*,-,+=,-=,.,T1,T2,T3,T4,T5,T6,T7,T8,
T9,T10,T11,T12,T13,T14,T15,&): T3&T4
New Password: min. 3 characters!
New Password:
Check Password: ok!
Explanation of Entries
A User Code uniquely addresses a KEY entry.
For the user code, 2,3 or 4 characters are accepted.
Caution:
DCS and VISONIK Insight both are case-sensitive.
This, however, is not true for DESIGO INSIGHT !
We thus recommend to enter the user code in either just small letters or just capital
letters to avoid conflicts in DESIGO INSIGHT.
Up to 21 characters can be used for name.
User Code
User Name