User Manual
Siemens Building Technologies VISONIK DCS Functions and System Messages VVS18 CM2Z8567E / 04.1999
Landis & Staefa Division Quick Guide - Working in Ctrl-V mode 1-11
1.6 Working in Ctrl-V mode
The Ctrl-V mode is the same as the new version of the Ctrl-D mode. In Ctrl-V mode, all
data points of a linked system can be displayed.
Proceed as follows to start the Ctrl-V mode:
Step Procedure Comment
1
CTRL+V Start Ctrl-V mode
2
Enter and confirm data point address Technical or user address
permitted.
Delete individual characters
using the backspace key or
delete the entire address
through direct entry.
3
> and enter and confirm parameter name
In Ctrl-V mode, the screen display is split. The upper half of the screen contains the
selected data point with the parameter list, the lower half is used for the DCS dialogue.
Terminal operation is as follows, whereby “
A01SB12
” is the user address:
DO =1=On: .
(Off,On), >
. DO A'01'SB12
ON PSe
DOK-Server
- ALsta Alarm Acknowledge Status = 2=Normal Unacknowledged
DO Set Digital Output: Priority=0 = 1=On
DO1 Set Digital Output: Priority=1 = On
DO2 Set Digital Output: Priority=2 = Off
- FBV Feedback Value = Off
- RDO Result. Digital Output from DOx = Off
----------------------------------------------------------------$52'010 (m5p1)
ctrl/V
Ctrl/P = Function Ctrl/K = Kill Display
Key = More Parameters
PageDown, PageUp
Use these keys to move up or down in the parameter list.
Use these keys to move up or down the highlighted section in the currently displayed
parameters. The respectively highlighted parameter appears on the first line where it
can also be changed, provided it is a writeable parameter.
+
or
-
Use these keys to increase or decrease the data point address by one on entering the
address. Caution: NumLock must be active
>
Entry of symbol ‘>’ plus e.g. parameter name or TRR; see below:
>Parameter name: increase displayed parameter list (max. 10 parameters)
>H Display of main parameters
>B Display of operating parameters
>K Display of configuration parameters
>S Display of service parameters
>TRR Display of the time reaction catalogue (TRR)
How do I proceed ?
Commands and
functions