User Manual
CM2U8567E / 04.1999 VISONIK DCS Functions and System Messages VVS18 Siemens Building Technologies
2-176 Function MRR Landis & Staefa Division
Example: Maintenance reaction entry
T8 11:48:12 Function=PNT : MRR
Operation =CH :
Reason =(UA,TA): $100'041
Entry =(1) 4 :
Status =. : 1
Accumulated Tot. =0 :
Maint. Hours =. : 1000
Maint. Date =. : .
Automatic Reset =No : Yes
Blocking Flag=. : No
Blocking Flag=. : $F10
Flag Value =Off : ?
Flag Value =(&,.,*,-,+=,-=,Off,Step 1,Step 2,Step
3): Step 1
Reaction =(UA,TA): ?
UA/TA = Change Point Parameter
CT = Printout Cleartext
MC = Issue MACRO Command
SLVM = Output Slave Message
CB = Start/Stop COLBAS Task
. = No Reaction (for MRR & GRR)
PICT = Auto Picture/Point Selection
Reaction =(UA,TA): $100'040
Parameter =DO :
Set Digital Output: Priority=0 =Off :
1.Further Address =. :
Message Mask =MSGDEV : ?
MSGDEV: M1
MM00: M1&M2
MM01: M1&M2
MM15: M1&M2
Message Mask =MSGDEV :
2.20.2 CH, Enter/Change Data
2.20.2.1 Changing an existing MRR entry
In order to change data in a reaction entry it must first be selected via its "reason" and
entry number. If the entry exists, it is listed completely for checking at the operating
terminal.
The edit mode then becomes active, so that the user can modify or confirm each part of
the reaction entry step by step.
A reaction entry is not changed (and re-saved) in the system until every step of this
dialogue has been completed, i.e. after the last prompt for "Message Mask" has been
answered. In all other cases, e.g. if the dialogue is exited with Ctrl/P or Ctrl/E, any
changed data will be lost.
Important: